Siemens FS720 Configuration page 221

Fire detection system
Table of Contents

Advertisement

Parameters
'Custom audio library ID'
Parameters
'Accept commands 'Fire
controls ON/OFF' from
FBF'
'Accept commands
'Sounders ON/OFF'' from
FBF'
'OFF allowed'
Building Technologies
Fire Safety
'Prioritized voice evac control' – parameters in the 'Overview' tab
Values
Numerical input field
Adjustment range:
[0]: Standard audio library
[1...2047]: ID number of the
user-defined audio library
'Prioritized voice evac control' – parameters in the 'Details' tab
Value
On/off
On/off
'Never'
'NOT if activated
automatically by causes'
'Always'
Description
The parameter determines which audio library
should be used by the devices assigned to the
control.
Note: The ID number configured here must
correspond to the imported ID numbers of the
assigned sounders in the 'Hardware' tree. If the ID
number does not match, the configuration tool
displays an error. If '0' is configured for the default
audio library, then the ID of the devices is irrelevant.
You will find more information on this in chapter
'Sounders and sounder bases (sounders, sounder
beacons, voice sounders) [➙ 126]'.
Description
The parameter defines that this control is a fire
control within the meaning of the VdS definition.
When the parameter is activated, all of the control's
effects can be switched off with the corresponding
button on the fire brigade operating panel (FBF).
Acoustic sounders connected to the control can be
switched off at any time using the corresponding
button on the fire brigade operating panel (FBF)
when the parameter is activated.
The parameter defines whether the control can be
switched off.
The following options can be configured:
Never
The control cannot be switched off if it was
activated automatically by its causes. The control
can only be switched off in the following
circumstances:
The control is in an idle state.
The control has been activated by a manual
command on the ↑ Person Machine
Interface.
The control has been activated by a 'Fire
control' element.
The control has been activated by a 'Time
control' element.
Always
'Control' task card
12
Evac control group
221 | 412
A6V10210424_j_en_--
2018-08-29