Siemens FS720 Configuration page 334

Fire detection system
Table of Contents

Advertisement

'Network' task card
14
Global BACnet configuration
334 | 412
Building Technologies
Fire Safety
Creating 'BACnet client supervision' element
1. Select 'Network' > ↑ 'Station' in the task card.
2. Create the 'BACnet client supervision' element for the 'Station' for each BACnet
client that is to be monitored. Link [➙ 68]
Assigning the 'BACnet client supervision' and 'BACnet client
configuration' elements
1. Highlight the 'BACnet client supervision' element in the tree view.
2. Open the 'Assign dialog' window.
a The 'BACnet client configuration' elements are highlighted in the list.
3. Select the corresponding element and click on 'Assign'.
Figure 157: Window 'Assign dialog' for assigning the element 'BACnet client supervision'
Determining 'Client supervision timeout'
Figure 158: 'BACnet client supervision' detail editor, 'Overview'
In the detail editor 'BACnet client supervision', 'Overview', the time after which a
fault message is displayed is defined in 'Client supervision timeout'.
The time period must match the ↑ BACnet client's query cycle, with which the
BACnet client queries the station's system status.
Set the value in the 'Client supervision timeout' field to one minute.
l
A6V10210424_j_en_--
2018-08-29