Siemens FS720 Configuration page 150

Fire detection system
Table of Contents

Advertisement

'Detection' task card
11
'Zone'
150 | 412
Building Technologies
Fire Safety
↑ Single-detector dependency and ↑ multi-detector dependency
The following table shows the required number of detectors with ↑ danger level
(GS) 2 or 3 in order to meet the criteria for 'PRE-STAGE'/'MAIN STAGE'' and to
trigger an alarm.
Template
'Single, standard'
'Single, no pre-alarm'
'Single, non-latching alarm'
'Single, ALARM sub-system' 1
'Single, Exting. discharged'
'Single, Exting. pre-alarm'
'Single, Gas alarm'
'Single, Gas warning'
'Single, door holders'
'Single, local ALARM'
'Multi, standard'
'Multi, garage'
'Multi, store'
'Multi, 2 det. dependency'
'Multi, ALARM sub-system'
'Multi, 2 det. dependency II'
[AT]
'Multi, 2 det. dependency III'
[CH]
'Two-zone dependency'
Table 6: Single-detector dependency and multi-detector dependency
Required number of detectors with danger level
(GS)
'PRE-STAGE'
GS 2
GS 3
1
0
0
0
0
0
0
1
0
1
0
1
0
1
0
0
0
1
0
1
0
0
0
1
0
0
1
0
1
0
1
0
1
0
1
'MAIN STAGE'
GS 2
GS 3
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
2
1
0
2
2
1
0
2
0
2
0
2
0
2
0
0
A6V10210424_j_en_--