'Control' task card
12
Evac control group
Parameters
'Enabled'
'Activation timeout'
'Enabled'
'Deactivation timeout'
Parameters
'Accept commands
'Sounders ON/OFF'' from
FBF'
'OFF allowed'
196 | 412
Building Technologies
Fire Safety
Values
On/off
Input field for time period
[hh:mm:ss]
Adjustment range: 0...30
sec
Increments: 1 sec
On/off
Input field for time period
[hh:mm:ss]
Adjustment range: 0...30
sec
Increments: 1 sec
'Universal sounder evac control' – parameters in the 'Details' tab
Value
On/off
'Never'
'NOT if activated
automatically by causes'
'Always'
Description
The parameter determines a defined time period.
Once this period has elapsed, the control is
automatically deactivated again, even if at least one
activation condition is still met.
The time period starts to run as soon as the system
activates the control.
Note: The 'Activation timeout' parameter and the
'Deactivation timeout' parameter cannot be activated
at the same time. The configuration tool displays an
error when both parameters are activated at the
same time.
The parameter determines a defined time period.
Once this period has elapsed, the control is
automatically activated again, even if no activation
condition is met.
The time period starts to run as soon as the system
deactivates the control.
Note: The 'Activation timeout' parameter and the
'Deactivation timeout' parameter cannot be activated
at the same time. The configuration tool displays an
error when both parameters are activated at the
same time.
Description
Acoustic sounders connected to the control can be
switched off at any time using the corresponding
button on the fire brigade operating panel (FBF)
when the parameter is activated.
The parameter defines whether the control can be
switched off.
The following options can be configured:
Never
The control cannot be switched off if it was
activated automatically by its causes. The control
can only be switched off in the following
circumstances:
The control is in an idle state.
The control has been activated by a manual
command on the ↑ Person Machine
Interface.
The control has been activated by a 'Fire
control' element.
The control has been activated by a 'Time
control' element.
Always
A6V10210424_j_en_--
2018-08-29