9.1.3

LED displays of the Ethernet interface

The Ethernet ports are equipped with LEDs to display Link and Activity.
Table 9-3
State of the Link and Activity LEDs
LED
LINK (upper LED)
ACT (lower LED)
9.1.4

LED displays of the CX32-2 controller extension

The different states that occur during power-up are indicated by the LEDs on the CX32-2
controller extension.
● The duration of the individual states varies.
● If an error occurs, the power-up is terminated and the cause is indicated accordingly via
the LEDs.
● At the end of an error-free power-up, all LEDs are switched off briefly.
● After power-up, the LEDs are controlled via the loaded software.
Table 9-4
Load software
LED
RDY
DP
Yellow
Yellow
Red
Red
Red 2 Hz
Red
Red 2 Hz
Red 2 Hz
Red
Yellow (flash‐
ing)
Red
Off
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
State
OFF
Lights up green
Lights up yellow
OFF
Flickers yellow
State
Reset
BIOS loaded
BIOS error
File error
FW loading
FW loaded
Meaning
No or faulty connection
Transfer rate 10 or 100 Mbit/s:
A different device is connected to port x and a physical connection
exists
Transfer rate 1,000 Mbit/s:
A different device is connected to port x and a physical connection
exists
No data exchange
Data exchange:
Data is being received or sent at port x
Comment
Hardware reset
All other LEDs light up yellow
-
Error occurred while loading the BIOS
● D4x5‑2 CompactFlash card not available or faulty
● Software on D4x5‑2 CompactFlash card not
available or faulty
RDY LED lights up red, DP LED flashes yellow without
fixed frequency
-
Diagnostics
9.1 Diagnostics via LED displays