Diagnostics
9.1 Diagnostics via LED displays
LED
RDY
DP
Off
Red
Red 0.5 Hz
Red 0.5 Hz
Table 9-5
Firmware
LED
RDY
DP
Yellow
Not relevant
Alternating
Table 9-6
CX32-2 – Description of the LEDs after ramp-up
LED
Color
RDY
-
(READY)
Green
Red
Red/
green
Yellow
Green/
yellow
or
red/yel‐
low
394
State
FW checked
(no CRC error)
FW checked
(CRC error)
State
Initializing
Running
State
Off
Electronic power supply is missing or outside the
permissible tolerance range.
Continuous
The component is ready for operation and cyclic
light
DRIVE‑CLiQ communication is taking place.
Flashing
Commissioning/reset
0.5 Hz
Flashing
Writing to the memory card
2 Hz
Flashing
General errors
2 Hz
Flashing
CX32‑2 is ready for operation.
0.5 Hz
However, software licenses are missing.
Flashing
Firmware update of the connected DRIVE-CLiQ
0.5 Hz
components running
Flashing
DRIVE-CLiQ component firmware update com‐
2 Hz
plete. Wait for POWER ON for the components in
question.
Flashing
Component detection via LED is activated
2 Hz
(p0124[0]).
Note:
Both options depend on the LED state when com‐
ponent detection is activated via p0124[0] = 1.
Comment
-
CRC invalid
Comment
See the table below
Description, cause
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
Remedy
Check power supply
Check parameterization/con‐
figuration data
Obtain licenses
Perform POWER ON for the
respective component