Commissioning (software)
7.5 Additional information on configuring the SINAMICS Integrated
Figure 7-33
HW Config - settings
The times are modified by changing the value in the "Factor" field.
SCOUT TIA
In order to parameterize the isochronous cycle clock for the PROFIBUS Integrated in the TIA
Portal, proceed as follows:
1. Select the PROFIBUS Integrated in the network view.
2. Select the "General" tab in the Inspector window and click "Equidistance" to display the
parameters for the isochronous PROFIBUS. The "Activate isochronous bus cycle" setting
is permanently selected and cannot be edited.
The other parameters are set to default settings and can be edited.