Commissioning (software)
7.2 Performing the configuration for the D4x5-2 offline
Procedure
While executing the wizard you will be prompted to perform, for example, the following
configuration steps:
1. In the "Option Module" dialog box, select whether you want to use a TB30 as option module.
Figure 7-1
Note
The TB30 is displayed as drive object below the Control Unit in the project navigator and
can be configured there.
2. In the "Insert Infeed" dialog box", select whether you want to use an infeed with or without
a DRIVE‑CLiQ connection. If the DC link has an external supply, select "No" (no
DRIVE‑CLiQ connection).
178
Selecting an option module
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
SIMOTION D4x5-2