Interconnecting The Infeed "Operation" Signal On The Cx32-2 - Siemens SIMOTION D4x5-2 Commissioning And Hardware Installation Manual

Hide thumbs Also See for SIMOTION D4x5-2:
Table of Contents

Advertisement

7.4.7.2

Interconnecting the infeed "Operation" signal on the CX32-2

Requirement
● Drive line-up with SIMOTION D4x5‑2 control unit and Line Module with DRIVE‑CLiQ
interface
● One or more CX32‑2 controller extensions without a Line Module of their own (i.e. the Motor
Modules of the D4x5‑2 and the CX32‑2 modules are supplied by the same DC link)
In this example, the Line Module must to be connected to the SIMOTION D4x5‑2 (not to the
CX32‑2).
For all other cases, see Section Using one infeed for several CUs (Page 269).
Procedure
When drives are created in Drive system 1, the signal "Closed-loop control operation" r0863.0
from the Line Module is automatically interconnected with the "Infeed operation" signal from
the drives (Drive 1...n) via p0864.
There is an internal communication channel available for the CX32‑2 controller extension (drive
system 2), via which the following signals from the SIMOTION D4x5‑2 control unit can be
automatically interconnected to the CX32‑2 controller extensions:
● "Closed-loop control operation" of the Line Module connected to the SIMOTION D4x5‑2
● Status of the SIMOTION D4x5‑2 onboard digital inputs (X122/X132, DI 0 ... 7 and DI/
DO 8 ... 15)
These signals are available on the CX32‑2 controller extension; since there is no need to
perform any additional configuration steps, it is very easy to make additional interconnections
with them within the CX32‑2.
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
Commissioning (software)
7.4 Configuring a CX32-2
221

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion cx32-2Simotion cbe30-2Simotion tb30

Table of Contents