Group objects
No.
118
This group object is enabled if the parameter Activate temperature limitation is set to Yes in the Temperature
controller – Basic-stage heating parameter window and the parameter Input for limit temperature sensor is
set to Via group object.
This group object is hidden in controller mode.
This group object receives the limit temperature for Basic-stage heating. The temperature value received
here is used to evaluate the limit temperature. The limit becomes active when the temperature set in the pa-
rameter Limit temperature is exceeded.
119
This group object is enabled if the parameter Activate temperature limitation is set to Yes in the Temperature
controller – Additional-stage heating parameter window and the parameter Input for limit temperature sensor
is set to Via group object.
This group object is hidden in controller mode.
This group object receives the limit temperature for Additional-stage heating. The temperature value received
here is used to evaluate the limit temperature. The limit becomes active when the temperature set in the pa-
rameter Limit temperature is exceeded.
120
This group object is enabled if the parameter Activate temperature limitation is set to Yes in the Temperature
controller – Basic-stage cooling parameter window and the parameter Input for limit temperature sensor is
set to Via group object.
This group object is hidden in controller mode.
This group object receives the limit temperature for Basic-stage cooling. The temperature value received
here is used to evaluate the limit temperature. The limit becomes active when the temperature set in the pa-
rameter Limit temperature is fallen below.
121
This group object is enabled if the parameter Activate temperature limitation is set to Yes in the Temperature
controller – Additional-stage cooling parameter window and the parameter Input for temperature limit sensor
is set to Via group object.
This group object is hidden in controller mode.
This group object receives the limit temperature for Additional-stage cooling. The temperature value received
here is used to evaluate the limit temperature. The limit becomes active when the temperature set in the pa-
rameter Limit temperature is fallen below.
Function
Basic-stage heating limit tem-
perature
Additional-stage heating limit
temperature
Basic-stage cooling limit tem-
perature
Additional-stage cooling limit
temperature
Group object name Data Type
Channel – Controller 2 bytes
DPT 9.001
Channel – Controller 2 bytes
DPT 9.001
Channel – Controller 2 bytes
DPT 9.001
Channel – Controller 2 bytes
SPT 9.001
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 354