ABB i-bus FCC/S 1 1 Series Product Manual page 243

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.7.2.1.4
Dependent Parameter
Monitor receipt of group object "Dew point alarm"
This parameter is only visible if the Device function parameter has been parameterized with the
Controller option.
This parameter is only visible if the Via group object option has been selected for the Dew point
status input parameter in the Application parameters parameter window.
Options:
The monitoring of the Dew point alarm group object is activated using this parameter. The regular
reception of the dew point alarm can be monitored using this parameter.
Deactivated: The monitoring of the Dew point alarm group object is deactivated.
Activated: The monitoring of the group object is active. The dependent parameter Time interval
for cyclical monitoring and the Error: dew point status receipt group object are enabled.
7.7.2.1.4.1
Dependent Parameter
Time interval for cyclical monitoring
Options:
The monitoring time within which the group object must be received is specified using this parame-
ter. Otherwise the Error: dew point status receipt alarm object is changed to alarm and the con-
troller reacts as if the dew point alarm were active. This means that the controller changes to the
Building Protection operating mode, which results in the closing of the cooling output. As long as
the fill level alarm is active, this mode for cooling cannot be left again. This state remains active un-
til a new value is received in the group object monitored that clears the alarm.
If the device is changed to the heating mode (on a device that is used for heating and cooling),
the device continues to function as before, without the alarm having any effect, because the
alarm only relates to cooling.
For more information on the dew point, see .
7.7.2.1.5
Dependent Parameter
Monitor receipt of group object "Fill level alarm"
This parameter is only visible if the Device function parameter has been parameterized with the
Controller option.
This parameter is only visible if the Via group object option has been selected for the Dew point
status input parameter in the Application parameters parameter window.
Options:
The monitoring of the Fill level alarm group object is activated using this parameter. The regular re-
ception of the fill level alarm can be monitored using this parameter.
Deactivated: The monitoring of the Fill level alarm group object is deactivated.
Activated: The monitoring of the group object is active. The dependent parameter Time interval
for cyclical monitoring and the Error: fill level status receipt group object are enabled.
Deactivated
Activated
00:00:30...00:05:00...18:12:15
Note
Deactivated
Activated
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 243