ABB i-bus FCC/S 1 1 Series Product Manual page 108

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.4.1.1.1.1.11
Dependent Parameter
Dew point status input
This parameter is not visible if the Device function parameter has been parameterized with the Ac-
tuator device option.
This parameter is not visible if the Basic-stage cooling parameter is deactivated.
Options:
This parameter is used to inform the integrated controller whether it is to include the dew point
alarm (Alarm/No alarm) in the control.
Deactivated: If Deactivated has been selected, the dew point alarm is not taken into account by
the controller.
Via physical device input: If this option is selected, the controller checks which of the physical
device inputs has been parameterized for a dew point sensor. The status of the dew point sen-
sor connected to this input is included in the control.
The message: Configure in 'Inputs' parameter window appears.
Only device inputs that have been parameterized as a dew point sensor are detected as such.
If no input has been parameterized as a dew point sensor, the function is considered deactivated.
If several inputs have been parameterized as a dew point sensor, there is a logical OR link be-
tween these inputs. As soon as one of the contacts signals the status "Dew point reached", the
controller evaluates the status as "Dew point alarm". Conversely, if none of the inputs signals the
status "Dew point reached", the controller evaluates the status as "No dew point alarm".
Via group object: The dew point alarm is received via a group object. The dependent Dew point
alarm group object appears. In addition, the dependent Dew point reached when parameter is
enabled.
Deactivated
Via physical device input
Via group object
Note
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 108