Send Status Values - ABB i-bus FCC/S 1 1 Series Product Manual

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.10.1.8

Send status values

Options:
This parameter defines when the fan output status values are to be sent. This parameter affects
the following fan output group objects:
Status Fan On/Off
Status Fan Speed
Status Fan Speed 1
Status Fan Speed 2
Status Fan Speed 3
Status Fan Automatic
If the parameter Switch fan speed via 1-bit objects is parameterized with the Deactivated option,
the group objects Status Fan Speed 1, Status Fan Speed 2 and Status Fan Speed 3 are not dis-
played.
On change: The values are sent on a change in the object values (e.g. change from 0 to 1).
With the Status Control value group object, the values are sent if the change in the control
value is at least 1 %.
Cyclically: If this option is selected, the status values are sent automatically after an adjustable
time has elapsed. The Every dependent parameter is displayed.
On change and cyclically: The values are sent on a change and cyclically.
On request: All status values are sent on the receipt of a command via the Request status
values group object.
After a change or request: The values are sent on request and on a change.
On request and cyclically: The values are sent on a change and cyclically.
After a change or request and cyclically: The values are sent on request and on a change and
cyclically. The Every dependent parameter is displayed.
7.10.1.8.1
Dependent Parameter
Every
Options:
This parameter is used to set the time after which the status values are to be sent cyclically. The
group objects are sent after each cycle.
On change
Cyclically
On change and cyclically
On request
After a change or request
On request and cyclically
After a change or request and cyclically
00:00:30...00:05:00...18:12:15
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 280