Parameters
7.7.2.1.2.2
Dependent Parameter
Operating mode after exceeding monitoring time
Options:
The selection made here defines which operating mode is to apply on the erroneous reception of
the Operating mode group object. This mode remains active until a new value is received in the
group object monitored.
7.7.2.1.3
Dependent Parameter
Monitor receipt of group object "Window contact"
This parameter is only visible if the Device function parameter has been parameterized with the
Controller option.
This parameter is only visible if the Via group object option has been selected for the Window
status input parameter in the Application parameters parameter window.
Options:
The monitoring of the Window contact group object is activated using this parameter. The regular
reception of the window status can be monitored using this parameter.
Deactivated: The monitoring of the Window contact group object is deactivated.
Activated: The monitoring of the group object is active. The dependent parameter Time interval
for cyclical monitoring and the Error: window status receipt group object are enabled.
7.7.2.1.3.1
Dependent Parameter
Time interval for cyclical monitoring
Options:
The monitoring time within which the group object must be received is specified using this parame-
ter. Otherwise the Error: window status receipt alarm object is changed to alarm and the controller
reacts as if the window were open. This means that the controller changes over to the Building
Protection mode. This mode remains active until a new value is received in the group object moni-
tored.
Building Protection
Comfort
Standby
Economy
Deactivated
Activated
00:00:30...00:05:00...18:12:15