ABB i-bus
KNX
Parameters
—
7.4.1.2.1.1.14.1
Dependent Parameter
Number of temperature input objects
This parameter is visible if, in the Temperature input parameter, the Via group object or Via physi-
cal device input and group object option has been selected.
Options:
This parameter is used to specify the number of group objects that can receive temperature values
via the bus.
•
1: If this option is selected, the External temperature 1 group object is enabled.
•
2: If this option is selected, the External temperature 1 and External temperature 2 group ob-
jects are enabled.
Using these two objects, temperature values measured using other devices can be received; these
values are then used to determine the actual temperature.
If the 1 option has been selected and in the Temperature input the Via physical device input and
group object option is not selected, the temperature received in the External temperature 1 group
object is the actual temperature. If the 2 option has been selected, the dependent parameters
Weighting of external measurement 1 and Weighting of external measurement 2 are enabled.
—
7.4.1.2.1.1.14.2
Dependent Parameter
Internal measurement weighting
This parameter is only visible if, in the Temperature input parameter, the Via physical device input
and group object option has been selected.
Options:
This value specifies the weighting with which the internal measurement is to flow into the calcula-
tion of the actual temperature.
—
7.4.1.2.1.1.14.3
Dependent Parameter
Weighting of external measurement 1
This parameter is only visible if both the following cases apply:
•
In the Temperature input parameter, the Via physical device input and group object option has
been selected.
•
In the Temperature input parameter, the Via group object option has been selected and in the
Number of temperature input objects parameter, the 2 option has been selected.
Options:
This value specifies the weighting with which the external measurement 1 is to flow into the calcu-
lation of the actual temperature.
1
2
0...100
0...100
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 138