ABB i-bus FCC/S 1 1 Series Product Manual page 250

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.8.1.1.1.2
Selection of Motor-driven (3-point)
7.8.1.1.1.2.1
Dependent Parameter
Reversing time
Options:
This parameter defines the reversing delay time of the valve drive.
The technical data for the valve drive must be observed.
7.8.1.1.1.2.2
Dependent Parameter
Switch on time for valve drive from 0 to 100 %
Options:
This parameter sets the time that the output switches on to move the valve drive or the valve from
0 % (closed) to position 100 % (fully opened).
The time required should be taken from the technical data of the valve.
7.8.1.1.1.2.3
Dependent Parameter
Automatic adjustment of valve drive
Options:
If the control value 0% is only rarely achieved in ongoing operation, this can lead to inaccuracies in
positioning control. This parameter activates automatic adjustment to move the valve drive in a de-
fined manner to the 0% position. This serves as the basis for position adjustment.
Yes: Automatic adjustment is activated. The dependent parameter Number of changes until
adjustment is displayed.
No: Automatic adjustment is deactivated.
50...500...1,000
Note
10...120...6,000
Note
No
Yes
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 250