7.12.1.1.8
Dependent Parameter
Reset manual adjustment via KNX when operating mode changes
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
No: When the device changes operating modes, the manual adjustment is cleared from active
parameters and replaced with the parametrized target temperature for the new mode plus any
change sent via the Base setpoint group object.
Example:
Comfort temperature 21 °C + manual adjustment 1.5 °C = 22.5 °C. Change to Eco mode with a
parametrized temperature of 17 °C. The device adjusts the temperature to 17 °C because the
manual adjustment has been cleared.
Yes: This option factors in the manual setpoint adjustment on top of the new operating mode
temperature.
Example:
Comfort temperature 21 °C + manual adjustment 1.5 °C = 22.5 °C. Change to Eco mode with a
parametrized temperature of 17 °C. The device adjusts the temperature to 18.5 °C because the
manual adjustment has been factored in.
7.12.1.1.9
Dependent Parameter
Reset manual adjustment via KNX using group object
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
When this option is activated, the manual adjustment can be cleared at any time via the Reset
manual setpoint adjustment group object.
Selecting Nohides this group object and you can no longer use it to reset manual setpoint adjust-
ment.
Example:
Resetting manual adjustment of all the devices in a building using a time scheduler in the system.
7.12.1.1.10
Dependent Parameter
Slave display indicates
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
This parameter determines whether a slave displays a setpoint as absolute or relative.
No
Yes
No
Yes
Absolute
Relative