ABB i-bus
KNX
Parameters
7.4.2.2.1.9
Fan output after ETS download
This parameter is only visible for:
FCC/S 1.3.1.1
FCC/S 1.3.2.1
FCC/S 1.5.1.1
FCC/S 1.5.2.1
Options:
This parameter is used to specify the fan speed that is to apply after a download.
Unchanged: The same fan speed as before the download. The status of the automatic mode
also remains unchanged. The fan follows the valve control value if the automatic mode is ac-
tive.
Applies control value: The speed is dependent on the valve control value, the automatic mode
is active. If the automatic mode was deactivated before the download, it is activated.
33 %: The fan runs with speed 33 % in the manual mode.
66 %: The fan runs with speed 66 % in the manual mode.
100 %: The fan runs with speed 100 % in the manual mode.
7.4.2.2.1.10
Relay output after ETS download
This parameter does not apply to FCC/S 1.4.1.1.
Options:
The reaction of the relay output after the download is specified using this parameter.
Unchanged: The relay remains in its actual position after the download.
On: The relay is switched on after the download.
Off: The relay is switched off after the download.
Unchanged
Applies control value
33 %
66 %
100 %
Unchanged
On
Off