ABB i-bus FCC/S 1 1 Series Product Manual page 227

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.6.4.2.3
Dependent Parameter
Increase for Standby cooling
This parameter is only visible if the device has been parameterized for cooling and the Deactivated
option has not been selected for the Basic-stage cooling parameter in the Application parameters
parameter window, and the No option has been selected for the Comfort heating setpoint =
Comfort cooling setpoint parameter.
Options:
This value defines the setpoint for the comfort cooling temperature. If the device is the type of op-
eration cooling and is changed to the Comfort operating mode, the device regulates to this temper-
ature.
The controller does not change the type of operation to reach this temperature, instead it ensures
this temperature is not exceeded on an increase in the actual temperature.
7.6.4.2.4
Dependent Parameter
Increase for Economy cooling
This parameter is only visible if the device has been parameterized for cooling and the Deactivated
option has not been selected for the Basic-stage cooling parameter in the Application parameters
parameter window, and the Setpoint specification and adjustment parameter has been parameter-
ized with the Relative option.
Options:
This parameter is used to set the temperature that is to apply in the Economy operating mode in
the type of operation cooling. This is defined here as the increase in relation to the comfort cooling
setpoint.
The controller does not change the type of operation to reach this temperature, instead it ensures
this temperature is not exceeded on an increase in the actual temperature.
0...2...15
Note
0...4...15
Note
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 227