Time interval for cyclical monitoring
Options:
The monitoring time within which the group object must be received is specified using this parame-
ter. Otherwise the Error: fill level status receipt group object is changed to alarm and the controller
reacts as if the fill level alarm were active. This means that the controller sets the control value for
cooling to 0. As long as the dew point alarm is active, this control value for cooling cannot be
raised again. This state remains active until a new value is received in the group object monitored
that clears the alarm.
If the device is changed to the heating mode (on a device that is used for heating and cooling),
the device continues to function as before, without the alarm having any effect, because the
alarm only relates to cooling.
For more information on the fill level, see .
7.7.2.1.6
Dependent Parameter
Monitor receipt of group object "Toggle heating/cooling"
The parameter is only visible if in the Heating/Cooling changeover parameter in the Application
parameters parameter window, the Via object only or Via object and automatically option has been
selected.
Options:
The monitoring of the Heating/Cooling changeover group object is enabled using this parameter.
The change in the type of operation can be monitored using this parameter.
Deactivated: The monitoring of the Heating/Cooling changeover group object is deactivated.
Activated: The monitoring of the group object is active. The dependent parameters Time
interval for cyclical monitoring and Heating/cooling mode when monitoring time exceeded as
well as the Error: heating/cooling receipt group object are enabled.
7.7.2.1.6.1
Dependent Parameter
Time interval for cyclical monitoring
Options:
The monitoring time within which the group object must be received is specified using this parame-
ter. Otherwise the Error: heating/cooling receipt alarm object is changed to alarm and the value set
in the Heating/cooling mode when monitoring time exceeded parameter applies.
00:00:30...00:05:00...18:12:15
Note
Deactivated
Activated
00:00:30...00:05:00...18:12:15