ABB i-bus FCC/S 1 1 Series Product Manual page 152

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.4.2.1.2.7
Fan output after ETS download
This parameter only applies to:
FCC/S 1.1.1.1
FCC/S 1.1.2.1
FCC/S 1.2.1.1
FCC/S 1.2.2.1
FCC/S 1.4.1.1
Options:
This parameter is used to specify the fan speed that is to apply after a download.
Unchanged: The same fan speed as before the download. The status of the automatic mode
also remains unchanged. The fan follows the valve control value if the automatic mode is ac-
tive.
Applies control value: The speed is dependent on the valve control value, the automatic mode
is active. If the automatic mode was deactivated before the download, it is activated.
1: The fan runs with speed 1 in the manual mode.
2: The fan runs with speed 2 in the manual mode.
3: The fan runs with speed 3 in the manual mode.
The Applies control value option is only available if it has not been deactivated in the Enable
automatic mode based on control value parameter in the Fan output window.
7.4.2.1.2.8
Fan output after ETS download
This parameter only applies to:
FCC/S 1.3.1.1
FCC/S 1.3.2.1
FCC/S 1.5.1.1
FCC/S 1.5.2.1
Options:
This parameter is used to specify the fan speed that is to apply after a download.
Unchanged: The same fan speed as before the download. The status of the automatic mode
also remains unchanged. The fan follows the valve control value if the automatic mode is ac-
tive.
Applies control value: The speed is dependent on the valve control value, the automatic mode
is active. If the automatic mode was deactivated before the download, it is activated.
33 %: The fan runs with speed 33 % in the manual mode.
66 %: The fan runs with speed 66 % in the manual mode.
100 %: The fan runs with speed 100 % in the manual mode.
The Applies control value option is only available if it has not been deactivated in the Enable
automatic mode based on control value parameter in the Fan output window.
Unchanged
Applies control value
1
2
3
Note
Unchanged
Applies control value
33 %
66 %
100 %
Note
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 152