Parameters
7.2.3.2
Dependent Parameter

In period

Options:
This parameter defines the number of telegrams sent by the device within a certain period of time.
The telegrams are sent as quickly as possible at the start of a period.
The device counts the number of telegrams sent within the parametrized period. As soon as the
maximum number of sent telegrams is reached, no further telegrams are sent on the KNX bus
until the end of the period. A new period commences at the end of the previous period. The tele-
gram counter is reset to zero, and sending of telegrams is allowed again. The current group ob-
ject value at the time of sending is always sent.
The first period (break time) is not precisely predefined. It can be anywhere between zero sec-
onds and the parametrized time. The subsequent sending times correspond with the
parametrized time.
Example:
Maximum number of sent telegrams = 5, period = 5 s. 20 telegrams are ready to send. The de-
vice immediately sends 5 telegrams. The next 5 telegrams are sent after a maximum of 5 sec-
onds. From this point, a further 5 telegrams are sent on the KNX every 5 seconds. The telegrams
are sent in the order in which they arise (first in - first out).
7.2.4

Enable group object "In operation" 1 bit

Options:
Yes: The group object is enabled.
No: The group object is not enabled.
1 second
2 seconds
5 seconds
10 seconds
30 seconds
1 minute
Note
No
Yes
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 90