No.
105
This group object is always visible in controller mode.
This group object is hidden in actuator mode.
The group object outputs the heating/cooling operating mode, active/inactive operation,
frost and heat alarm, as well as any malfunction (failure of actual temperature measurement) according to
the specification
for the RHCC (Room Heating Cooling Controller) status.
106
This group object is always visible in controller mode.
This group object is hidden in actuator mode.
This group object must be connected to the slave's group object of the same name. The group object syn-
chronizes between the controller (master) and the slave.
The group object transmits the current operating mode, heating/cooling operating mode,
active/inactive operation, frost alarm and the dew point alarm to the slave.
The group object synchronizes the heating/cooling status between the controller (master) and the slave.
107
This group object is always visible in controller mode.
This group object is hidden in actuator mode.
This group object outputs the currently valid HVAC operating mode after evaluation of all priorities and influ-
ences. The group object indicates the current controller operating mode.
The group object sends the current operating mode as a 1-byte value.
Telegram value:
108
This group object is enabled if the parameter Setpoint specification and adjustment is set to Absolute and
Comfort heating setpoint = Comfort cooling setpoint is set to No in the Setpoint manager parameter window.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Comfort heating. The value re-
ceived via this group object is permanently stored and serves as the new Comfort heating setpoint. Manual
setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
108
This group object is enabled if the parameter Setpoint specification and adjustment is set to Absolute and the
parameter Comfort heating setpoint = Comfort cooling setpoint is set to Yes in the Setpoint manager parame-
ter window.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Comfort heating and cooling.
The value received via this group object is permanently stored and serves as the new Comfort heating and
cooling setpoint. Manual setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
Function
Controller RHCC status
Controller HVAC status (mas-
ter)
Current HVAC operating mode Channel – Controller 1 bit
1: Comfort
2: Standby
3: Economy
4: Frost/heat protection
Comfort heating setpoint
Setpoint for Comfort heating
and cooling
Group object name Data Type
Channel – Controller 2 bytes
DPT 22.101
Channel – Controller 1 byte
DPT 5.001
DPT 20.102
Channel – Controller 2 bytes
DPT 9.001
Channel – Controller 2 bytes
DPT 9.001
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 351
Flag
C, R, T
C, R, T
C, R, T
C, W
C, W