ABB i-bus FCC/S 1 1 Series Product Manual page 353

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Group objects
No.
113
This group object is enabled if the parameter Setpoint specification and adjustment in the Setpoint manager
parameter window is parametrized with Absolute.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Standby cooling. The value re-
ceived via this group object is permanently stored and serves as the new Standby cooling setpoint. Manual
setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 10...40 °C. A value outside this range is limited to this range.
The value must be greater than the value for comfort cooling. If a value is not below this value, the device will
automatically classify it below this value.
114
This group object is enabled if the parameter Setpoint specification and adjustment in the Setpoint manager
parameter window is parametrized with Absolute.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for building protection heating (frost
protection). The value received via this group object is permanently stored and serves as the new building
protection heating setpoint. Manual setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 5...15 °C. A value outside this range is limited to this range.
The value must be less than the value for comfort heating. If a value is not below this value, the device will
automatically classify it below this value.
115
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for building protection cooling (heat
protection). The value received via this group object is permanently stored and serves as the new building
protection cooling setpoint. Manual setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 27...45 °C. A value outside this range is limited to this range.
The value must be greater than the value for comfort cooling. If a value is not below this value, the device will
automatically classify it below this value.
116
This group object is enabled if, in actuator mode, the parameter Basic-stage heating is set to Fan Coil Unit in
the Application parameters parameter window.
This group object is hidden in controller mode.
This group object receives the control value for heating in actuator mode.
This control value is issued on the selected output when heating operation is active.
117
This group object is enabled if, in actuator mode, the parameter Basic-stage cooling is set to Fan Coil Unit in
the Application parameters parameter window.
This group object is hidden in controller mode.
This group object receives the control value for cooling in actuator mode.
This control value is issued on the selected output when cooling operation is active.
Function
Standby cooling setpoint
Building protection heating set-
point
Building Protection cooling set-
point
Heating control value
Cooling control value
Group object name Data Type
Channel – Controller 2 bytes
DPT 9.001
Channel – Controller 2 bytes
DPT 9.001
Channel – Controller 2 bytes
DPT 9.001
Channel – Actuator
1 byte
DPT 5.001
Channel – Actuator
1 byte
DPT 5.001
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 353