ABB i-bus
KNX
Parameters
7.8.1.1.1.3.2
Dependent Parameter
Open if control value greater than or equal to
Options:
The output switches ON continuously if the value parameterized here is greater than or equal to
the received control value. If a control value less than the parameterized value is received, the out-
put switches OFF.
7.8.1.1.1.3.3
Dependent Parameter
Valve drive opening/closing time
This parameter is visible if, in the Valve output parameter, the Thermoelectric (PWM) or Open/
Close signal option has been selected.
Options:
With this parameter, a time is set in seconds that the connected valve requires to move from posi-
tion 0 % (valve closed) to position 100 % (valve fully open), or the valve requires to move from
100 % to 0 %.
The time should be taken from the technical data of the valve, and it corresponds with the total
runtime.
7.8.1.1.2
Send status values
Options:
This parameter defines when the valve output status value are to be sent. It affects the group ob-
jects Status byte valve A, Fault: valve output A and Status Control value for the valve drive.
On request: The valve output status values are sent on the receipt of a command via the
Request status values group object.
On change: The values are sent on a change in the object values (e.g. change from 0 to 1).
With the Status Control value group object the values are only sent if the change in the control
value is at least 1 %.
Cyclically: If this option is selected, the status values are sent automatically after an adjustable
time has elapsed. The Every dependent parameter is displayed.
After a change or request: The values are sent on request and on a change.
After a change or request and cyclically: The values are sent on request and on a change and
cyclically. The Every dependent parameter is displayed.
7.8.1.1.2.1
Dependent Parameter
Every
Options:
This parameter is used to set the time after which the status values are to be sent cyclically. The
group objects are sent after each cycle.
1...100
10...60...900
Note
On request
On change
Cyclically
After a change or on request
After a change or request and cyclically
00:00:30...00:05:00...18:12:15
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 252