3.11.4.6

Rated current output 16 A

Rated values
Switching currents
Service life
Switching times
3.11.4.7

Fan output (analog)

Rated values
Number
U
rated voltage
n2
I
rated current (per output pair)
n2
AC3* operation (cos ϕ = 0.45) to EN 60947-4-1 16 A / 230 V AC
AC1* operation (cos ϕ = 0.8) to EN 60947-4-1
Minimum switching capacity at 100 mA
DC current switching capacity, resistive load, at
16 A
Mechanical service life
Electrical endurance of switching contacts to
IEC 60947-4-1
AC1* (240 V/cos ϕ=0.8)
Maximum relay position change per output and
minute if only one relay is switched.
Number
Control signal
Signal type
Output load
Output tolerance
Current limitation
1
250 V AC (50/60 Hz)
16 A (resistive load for additional heater)
16 A / 230 V AC
24 V AC
24 V DC
> 3 x 10⁶ cycles
> 10⁶ cycles
> 10⁵ cycles
> 500
1, non-isolated, short-circuit proofed
0...10 V DC
Analog
> 10 kohms
± 10%
max. 1.5 mA
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 77