Parameters
7.7.1.1.2.2
Dependent Parameter
Fan output / Fan output for forced operation ON / Fan output for forced operation OFF
This parameter only applies to:
FCC/S 1.1.1.1
FCC/S 1.1.2.1
FCC/S 1.2.1.1
FCC/S 1.2.1.1
FCC/S 1.4.1.1
Options:
This parameter is used to specify the fan speed that is to apply with forced operation active (for 2-
bit in the related state, ON or OFF).
Unchanged: The same fan speed as before the activation of the forced operation applies.
Applies control value: The speed is dependent on the valve control value. The automatic mode
is active.
1: The fan runs at speed 1.
2: The fan runs at speed 2.
3: The fan runs at speed 3.
The Applies control value option is only available if it has not been deactivated in the Enable
automatic mode based on control value parameter in the Fan output window.
Unchanged
Applies control value
1
2
3
Note
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 237