ABB i-bus FCC/S 1 1 Series Product Manual page 168

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.5.1.6.1
Basic-stage heating control value type
Options:
This parameter is used to specify the control and control value type for the basic-stage heating.
The standard value for the parameter is dependent on the selection in the Basic-stage heating and
Actuate basic-stage heating via parameters (Application parameters parameter window).
On the selection of one of the physical device outputs for the actuation of the basic-stage heating
or on output via KNX group object, the controller has a fixed pre-configuration that cannot be
changed. The pre-configured controller type is dependent here on the option selected in the Basic-
stage heating parameter.
The only exception is on the selection of Free configuration. In this situation, everything can be se-
lected and set freely.
The following table shows the dependencies:
Option selected:
Basic-stage heating
Convector (e.g. radiator)
Area (e.g. floor heating)
Electric heater (in room)
Free configuration
Fan coil unit: electric heater (in fan
coil unit)
Fan coil unit: Water heating coil
2-point 1 bit (On/Off)
2-point 1 byte (0/100 %)
PI continuous (0...100 %)
PI PWM (On/Off)
PI continuous (0...100 %) for Fan Coil
Pre-configured controller type:
type of heating control value
PI continuous (0...100 %)
PI continuous (0...100 %)
2-point 1 bit (On/Off)
PI continuous (0...100 %)
2-point 1 bit (On/Off)
PI continuous (0...100 %) for Fan
Coil
Controller type can be
changed
No
No
No
Yes
No
No
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 168