Parameters
7.13.1.4.5.1
Dependent Parameter
Value is sent from a change of
This is displayed if the Send temperature value parameter option includes After a change.
Options:
This parameter determines the temperature change that triggers sending the output value.
7.13.1.4.5.2
Dependent Parameter
Every
This is displayed if the Send temperature value parameter option includes cyclically.
Options:
The interval for cyclic sending is set with this additional parameter.
7.13.1.5
Binary signal input
7.13.1.5.1
Dependent Parameter
Maximum dead time
The maximum dead time is 200 ms.
The maximum dead time prevents unwanted multiple operations on the input, e.g. due to bouncing
of the contact.
7.13.1.5.1.1
What is maximum dead time?
An edge change at the input is evaluated with a maximum dead time (delay) of 200 ms. This time
may vary from 0–200 ms.
No further bouncing is possible.
00.2...01.0...10.0
00:00:30...18:12:15
Note
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 308