ABB i-bus
KNX
Group objects
No.
83
This group object is always enabled in controller mode.
This group object is hidden in actuator mode.
This group object can receive the presence status (person in the room) via KNX.
Telegram value:
When the presence information is received, this group object changes the device's operating mode to Com-
fort. When the room vacant information is received the operating mode is set back to the operating mode set
via the group object Operating mode.
A higher-priority group object can override the operating mode.
If a slave is used:
To indicate the operating mode on a slave, the group address associated with this group object must
also be connected to the slave's group object Presence detector (slave).
84
This group object is enabled if the controller was parametrized for heating. For this purpose, Deactivated
must not be selected for the parameter Basic-stage heating in the Application parameters parameter window.
This group object is hidden in actuator mode.
The device uses the group object to indicate whether it is currently active in the operating mode, i.e. whether
the control value is greater than 0.
Telegram value:
85
This group object is enabled if the controller was parametrized for cooling. For this purpose, Deactivated
must not be selected for the parameter Basic-stage cooling in the Application parameters parameter window.
This group object is hidden in actuator mode.
The device uses the group object to indicate whether it is currently active in the operating mode, i.e. whether
the control value is greater than 0.
Telegram value:
Function
Presence detector (master/
slave)
0: Room vacant
1: 1: Room occupied
Note
Status Heating
0: Heating control value = 0
1: Heating control value > 0
Status Cooling
0: Cooling control value = 0
1: Cooling control value > 0
Group object name Data Type
Channel – Controller 1 bit
DPT 1.018
Channel – Controller 1 bit
DPT 1.001
Channel – Controller 1 bit
DPT 1.001
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 342
Flag
C, W
C, R, T
C, R, T