Group objects
No.
23
This group object is enabled if the parameter Fan speed limitation is set to Activated in the Fan output pa-
rameter window.
Limitation 1 is active when a telegram with the value 1 is received on the group object Limitation 1. Limitation
1 is canceled when a telegram with the value 0 is received on the group object Limitation 1.
When Limitation 1 is activated, the fan can assume the only the fan speed or speed range as set in the pa-
rameter Limitation 1.
Telegram value:
24
See group object 23
25
See group object 23
Function
Limitation 1
0 = Limitation x inactive
1 = Limitation x active
Limitation 2
Limitation 3
Group object name Data Type
Channel – Fan
1 bit
DPT 1.003
Channel – Fan
1 bit
DPT 1.003
Channel – Fan
1 bit
DPT 1.003
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 327
Flag
C, W
C, W
C, W