Technical Data; General Technical Data - ABB i-bus FCC/S 1 1 Series Product Manual

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Product Overview
3.10.4

Technical data

3.10.4.1

General technical data

Supply
Terminals
Connection terminals
Protection degree and class
Isolation category
SELV
Temperature range
Ambient conditions
Design
Dimensions
Mounting
Approvals
Bus voltage
Current consumption, bus
Leakage loss, bus
Leakage loss, device
KNX connection
Relay 16 A
Electronic outputs
KNX
Inputs/Outputs
Screw terminal
Wire end ferrule without plastic sleeve
Wire end ferrule with plastic sleeve
TWIN ferrules
Wire end ferrule contact pin length
Tightening torque
Grid
Degree of protection
Protection class
Overvoltage category
Pollution degree
KNX safety extra low voltage
Operation
Transport
Storage
Maximum air humidity
Atmospheric pressure
Modular installation device (MDRC)
Design
Housing/color
Dimensions
Mounting width in space units
Mounting depth
35 mm mounting rail
Mounting position
Weight
Fire classification
KNX certification
Certification
CE marking
21...32 V DC
< 12 mA
Maximum 250 mW
Maximum 3 W
0.25 W
1.0 W
1.2 W
Via bus connection terminal
Via screw terminals
Screw terminal with universal head (PZ 1)
0.2...4 mm² stranded, 2 x (0.2...2.5 mm²)
0.2...6 mm² single core, 2 x (0.2...4 mm²)
0.25...2.5 mm²
0.25...4 mm²
0.5...2.5 mm²
Min. 10 mm
Max. 0.6 Nm
6.35
IP 20 to EN 60529
II to EN 61140
III to EN 60664-1
II to EN 60664-1
SELV 24 V DC
-5...+45°C
-25...+70°C
-25...+55°C
93%, no condensation allowed
Atmosphere up to 2,000 m
Modular installation device
ProM
Plastic housing, gray
90 x 105 x 63.5 mm (H x W x D)
6x 17,5 mm modules
63.5 mm
To EN 60715
Any
0.21 kg
Flammability V-0 as per UL94
To EN 50491
To EN 60669
In accordance with the EMC directive and low
voltage directive