ABB i-bus FCC/S 1 1 Series Product Manual page 294

Knx fan coil controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.12.1.1.2
Dependent Parameter
Max. manual reduction in heating mode via KNX
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
The parameter determines the maximum setpoint reduction that can be manually set via KNX in
Heating mode. Use the Request setpoint adjustment group object to reduce the Comfort heating
setpoint by a maximum of the value set here.
If the object receives a value below this, the maximum possible reduction is applied, and a re-
quest with the new temperature is confirmed on the Confirm setpoint adjustment group object.
7.12.1.1.3
Dependent Parameter
Max. manual increase in cooling mode via KNX
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
The parameter determines the maximum setpoint increase that can be manually set via KNX in
Cooling mode. Use the Request setpoint adjustment group object to increase the Comfort cooling
setpoint by a maximum of the value set here.
If the object receives a value that exceeds this, the maximum possible increase is applied, and a
request with the new temperature is sent via KNX on the Confirm setpoint adjustment group ob-
ject.
7.12.1.1.4
Dependent Parameter
Max. manual reduction in cooling mode via KNX
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
The parameter determines the maximum setpoint reduction that can be manually set via KNX in
cooling mode. You can use the Request setpoint adjustment group object to reduce the Comfort
cooling setpoint by a maximum of the value set here.
If the object receives a value below this, the maximum possible reduction is applied, and a re-
quest with the new temperature is confirmed on the Confirm setpoint adjustment group object.
0...3...9
Note
0...3...9
Note
0...3...9
Note
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 294