7.13.1.5.2.2.2
Dependent Parameter
Long operation after
Options:
The time period T
7.13.1.5.3
Dependent Parameter
Enable group object "Block" 1-bit
Options:
Yes: Enables the 1-bit group object Block. This can be used to disable the input.
If the input is disabled and the option Send cyclically is set, the last state is still sent regardless of
the block. The Block option blocks the physical input; sending continues internally.
When the input is blocked there is essentially no reaction to a signal change on the input, but:
If the input state changes during the block phase, the new group object value is sent immediately
after the block is released. If the input state remains the same during the block phase, the group
object value is not sent.
The minimum signal duration does not start until the Block has finished.
Block is deactivated after an ETS reset, a bus voltage recovery or a download.
01.0...10.0
after which an operation is considered long is defined here.
L
No
Yes
Note
Note
Waiting for a long button push or a minimum signal duration is suspended
Parameterized cyclic sending is not interrupted
It is still possible to write the Switch group object.
Note
Note