ABB i-bus
KNX
Parameters
—
7.5.1.6.1.1.2.2
Dependent Parameter
Hysteresis
Options:
This parameter is used to specify the hysteresis that is to apply to the setpoint to prevent continu-
ous switching of the controller.
•
Upper switching point = setpoint + hysteresis
•
Lower switching point = setpoint – hysteresis
Heating controller:
•
If the actual temperature is below the lower switching point, the controller switches on.
•
If the actual temperature is above the upper switching point, the controller switches off.
Cooling controller:
•
If the actual temperature is below the lower switching point, the controller switches off.
•
If the actual temperature is above the upper switching point, the controller switches on.
—
7.5.1.6.1.1.2.3
Dependent Parameter
Send control value cyclically (0 = cyclical sending disabled)
This parameter is only visible on the selection of the PI continuous (0...100 %) or PI continuous
(0...100 %) for Fan Coil option.
Options:
This parameter is used to specify the cycle time with which the control value is to be sent.
On the selection of the value 0, cyclic sending is deactivated.
—
7.5.1.6.1.1.2.4
Dependent Parameter
Activate temperature limitation
Options:
A controller limit temperature can be activated using this parameter. Using the limit temperature,
the controller's control value for this stage can be set to 0 on reaching a parameterized tempera-
ture. In this way, exceeding (heating) or dropping below (cooling) this temperature can be pre-
vented.
An example of the usage of the limit temperature is floor heating, where exceeding a specific tem-
perature must be prevented to protect the material of the floor.
•
No: The limit temperature is deactivated.
•
Yes: The limit temperature is activated. The following dependent parameters are also dis-
played.
0.3...0.5...25.5
0...15...60
No
Yes
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 171