Product Overview
Button/LED
Open/close relay output
Fan speed
Manual operation
Inputs a...x
Table 16: Operating and display elements – KNX operation
Description/Function
Button without function
Button without function
Activate manual operation by
pressing and holding the button (for
at least 5 seconds).
LED indication depending on how
the inputs are used.
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 53
LED indicator
On: Contact closed
Off: Contact open
Indication of the current fan speed
with speed switching:
Speed 0: all LEDs off
Speed 1: LED 1 on
Speed 2: LEDs 1 &2 on
Speed 3: all LEDs on
Indication of the current fan speed
with changeover switching:
Speed 0: all LEDs off
Speed 1: LED 1 on
Speed 2: LED 2 on
Speed 3: LED 3 on
On: On: The device is in Manual
Off: Device is in KNX mode
Flashing when button is pressed:
Manual operation has been deacti-
vated via ETS parameters
Binary sensor:
LED on: Contact closed
LED off: Contact open
Temperature sensor:
LED on: Temperature sensor
connected
LED flashing: Error (cable
break/short circuit)
Analog room control unit
LED on: Analog room control
unit connected
LED flashing: Error (cable
break/short circuit)