Parameters
7.4.2.2.2.3.1
Dependent Parameter
Control value
Options:
This parameter is used to specify the control value that is to apply after bus voltage recovery until a
new control value is received.
7.4.2.2.2.4
Reaction on bus voltage recovery Fan output
This parameter is only visible for:
FCC/S 1.1.1.1
FCC/S 1.1.2.1
FCC/S 1.2.1.1
FCC/S 1.2.2.1
FCC/S 1.4.1.1
Options:
This parameter is used to specify the fan speed that is to apply after bus voltage recovery.
Unchanged: The same fan speed as before/during the bus voltage failure applies. The status of
the automatic mode also remains unchanged. The fan follows the valve control value if the au-
tomatic mode is active.
Applies control value: The speed is dependent on the valve control value. The automatic mode
is active. If the automatic mode was deactivated before the download, it is activated.
1: The fan runs with speed 1 in the manual mode.
2: The fan runs with speed 2 in the manual mode.
3: The fan runs with speed 3 in the manual mode.
The Applies control value option is only available if it has not been deactivated in the Enable
automatic mode based on control value parameter in the Fan output window.
0...100
Unchanged
Applies control value
1
2
3
Note
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 160