ABB i-bus
KNX
Parameters
7.4.2.1.1.10
Fan output after ETS download
This parameter is only visible for:
•
FCC/S 1.3.1.1
•
FCC/S 1.3.2.1
•
FCC/S 1.5.1.1
•
FCC/S 1.5.2.1
Options:
This parameter is used to specify the fan speed that is to apply after a download.
•
Unchanged: The same fan speed as before the download. The status of the automatic mode
also remains unchanged. The fan follows the valve control value if the automatic mode is ac-
tive.
•
Applies control value: The speed is dependent on the valve control value, the automatic mode
is active. If the automatic mode was deactivated before the download, it is activated.
•
33 %: The fan runs with speed 33 % in the manual mode.
•
66 %: The fan runs with speed 66 % in the manual mode.
•
100 %: The fan runs with speed 100 % in the manual mode.
7.4.2.1.1.11
Relay output after ETS download
This parameter does not apply to FCC/S 1.4.1.1.
Options:
The reaction of the relay output after the download is specified using this parameter.
•
Unchanged: The relay remains in its actual position after the download.
•
On: The relay is switched on after the download.
•
Off: The relay is switched off after the download.
Unchanged
Applies control value
33 %
66 %
100 %
Unchanged
On
Off
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 148