01

01 Actual values

01.01
Motor speed
used
-30000.00...
30000.00 rpm
01.02
Motor speed
estimated
-30000.00...
30000.00 rpm
01.03
Motor speed %
-1000.00...
1000.00%
01.06
Output frequency
-500.00...
500.00 Hz
01.07
Motor current
0.00...
30000.00 A
01.08
Motor current %
of motor nom
0.0...1000.0%
Description
Basic signals for monitoring the drive.
All parameters in this group are read-only unless
otherwise noted.
Note: Values of these actual signals are filtered
with the filter time defined in group
settings. The selection lists for
Monitoring/scaling
parameters in other groups mean the raw value
of the actual signal instead. For example, if a
selection is "Output frequency" it does not point
to the value of parameter
but to the raw value.
Shows estimated motor speed.
A filter time constant for this signal can be
defined by parameter
speed.
Estimated motor speed.
Shows estimated motor speed in rpm.
A filter time constant for this signal can be
defined by parameter
speed.
Estimated motor speed.
Shows motor speed in percent of the
synchronous motor speed.
Motor speed.
Shows estimated drive output frequency in Hz.
A filter time constant for this signal can be
defined by parameter
frequency.
Estimated output frequency.
Shows measured (absolute) motor current in A.
Motor current.
Shows motor current (drive output current) in
percent of the nominal motor current.
Motor current.
46
01.06 Output frequency
46.11 Filter time motor
46.11 Filter time motor
46.12 Filter time output
Parameters 83
Def/
FbEq16
-
1 = 1 rpm
-
1 = 1 rpm
-
10 = 1%
-
10 = 1 Hz
-
1 = 1 A
-
1 = 1%