Error Diagnostics; Table 37: Diagnostic Messages - WAGO 8FDI 24V PROFIsafe 750-662/000-004 Manual

Table of Contents

Advertisement

84
Diagnostics
8.4

Error Diagnostics

Diagnostic signaling of the F I/O module not a safety-related feature
Diagnostic signaling of the F I/O module cannot be part of the safety function
under any circumstances.
After detecting internal or external errors, the F I/O module outputs diagnostic
messages to the safe PLC via the fieldbus. Errors can be identified by the
diagnostic messages, and appropriate troubleshooting measures can be taken.
The F I/O module provides diagnostic messages via the indicators and the
diagnostic services of the PROFINET fieldbus system.
All diagnostic messages that the F I/O module makes available are listed below
in alphabetical order. The structure of the diagnostic messages is described in
the fieldbus coupler manuals.
The F I/O module 750-662/000-004 can be operated on the WAGO I/O
System 750 fieldbus couplers specified in section "Technical Data" > ... >
"Communication":

Table 37: Diagnostic Messages

Message
Acknowledge-
ment required
Discrepancy time
exceeded
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Diagnostic type Module diagnostic
Coding
0x004F
LED indicator
PROFIsafe status: green, flashing at
0.5 Hz
Description/
Acknowledgement required to reactivate
remedy
the channel(s) after error correction. This
diagnostic is only output in PROFIsafe
V2.6 mode.
Classification
Error
Diagnostic type Channel diagnostics
Coding
0x021E
LED indicator
Module error: red, channel status
according to input value
Description/
For two-channel analysis of the input pair,
remedy
the F I/O module has determined that the
discrepancy time set has been exceeded.
Check the safety function. Adjust the
discrepancy time setting if necessary.
Classification
Error
WAGO I/O System
750-662/000-004 8FDI 24V PROFIsafe
Description

Advertisement

Table of Contents
loading

Table of Contents