Short Circuit Test Ix Parameter; Table 28: Input / Clock Output Assignment - WAGO 750-666/000-003 Manual

Wago-i/o-system 750 4fdi/2fdo 24v/10a profisafe v2 ipar, 4-channel digital input and 2-channel digital output module profisafe v2 ipar, 24v/10a semiconductor power output
Hide thumbs Also See for 750-666/000-003:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
7.4.5.2

Short circuit Test Ix Parameter

Protect signal lines when installing!
When connecting signal lines to the digital inputs of the PROFIsafe I/O module,
make sure that only the following signals are transmitted within a cable or non-
metallic sheathed cable:
Those whose short circuit does not lead to a dangerous failure of the safety
function
Those supplied by different clock outputs
Therefore, please make sure that the signal lines are installed in accordance with
EN 60204-1 or EN ISO 13849-2 (e.g., as separate sheathed lines or in separate
cable ducts).
The digital inputs are tested cyclically by the PROFIsafe I/O module. If the Short
circuit test parameter is set to the "not active" value, then the PROFIsafe I/O
module only tests the input circuit for internal errors. You have to set the Short
circuit test parameter to "not active" if, for example, you connect the
semiconductor output of a sensor (such as light arrays, light barriers, etc.) to the
digital input of the PROFIsafe I/O module.
If you set the Short circuit test parameter to the "active" value, then you have to
connect the digital input to the associated clock output via a switching element
(e.g., break contact). By doing so, the PROFIsafe I/O module tests the signal line
for short circuits against external voltages. If the short circuit test detects an
external voltage on the digital input, the PROFIsafe I/O module is passivated and
the "Short circuit" diagnostic message is output to the safe PLC.

Table 28: Input / clock output assignment

Inputs
I1, I3
I2, I4
Using the cyclical tests of the digital inputs, the PROFIsafe I/O module detects the
following errors on the digital inputs:
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Associated clock output (for activated short circuit test)
Commissioning
T1
T2
103