The following table lists the safe response times in the event of failure that result
from the input filter time set.

Table 21: Safe response time of the digital inputs in the event of failure

Input
filter time
0 ms
0.5 ms
1 ms
2 ms
3 ms
5 ms
10 ms
20 ms
50 ms
100 ms
200 ms
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Standard operating mode
Single-
Valence
channel
evaluation
analysis
equivalent
35 ms
35 ms
36 ms
36 ms
38 ms
38 ms
42 ms
42 ms
47 ms
47 ms
59 ms
59 ms
89 ms
89 ms
150 ms
150 ms
331 ms
331 ms
633 ms
633 ms
1237 ms
1237 ms
Device Description
Rotary table
Valence
operating
evaluation
mode
antivalent
19 ms
35 ms
20 ms
36 ms
21 ms
38 ms
24 ms
42 ms
28 ms
47 ms
36 ms
59 ms
56 ms
89 ms
96 ms
150 ms
217 ms
331 ms
419 ms
633 ms
821 ms
1237 ms