Summary of Contents for ITW Dynatec DYNAMELT D15 Series
Page 1
Adhesive Application Solutions | ISO 9001 certified DYNAMELT D15/D25/D45 SERIES ADHESIVE SUPPLY UNIT with V6 DynaControl with LCD or Touch Screen Controller Rev.1.16 Technical Documentation, No.20-63, Rev.9.16 ITW Dynatec An Illinois Tool Works Company www.itwdynatec.com...
Page 2
Please be sure to include the serial number of your application system each time you order replacement parts and/or supplies. This will enable us to send you the correct items that you need. ITW Dynatec Service Parts and Technical Service: AMERICAS EUROPE, MIDDLE ASIA PACIFIC EAST &...
Safety Precautions Page 1-1 ITW Dynatec Revised 10/14 ALL MODELS Chapter 1 SAFETY PRECAUTIONS All operators and service personnel must read and understand this manual before operating or servi- cing equipment. All maintenance and service on this equipment must be performed by trained technicians.
For this reason, always wear eye protection and protective clothing. Either of the two High Pressure symbols shown may be used on ITW Dynatec equipment. Protective Covers...
Never operate this unit in an explosive environment. Use cleaning compounds recommended by ITW Dynatec or your adhesive supplier only. Since the flash points of clean- ing compounds vary according to their composition, consult with your supplier to determine the maximum heating tem- peratures and safety precautions.
Most importantly, when over-heated, many HMPURs release gases that can be hazardous to humans. Therefore, adequate vent- ilation must be available to prevent injury to personnel in the workspace. ITW Dynatec PN 114367 Vent Hood is re- quired.
Description Page 2-1 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Chapter 2 DESCRIPTION AND SPECIFICATIONS Description The D15/D25/D45 Series adhesive supply units (ASUs) are computer-controlled hot-melt supply units designed on metric standards. Their “all-icon” control panels, with choice of display lan- guages, are internationally operator friendly.
Description Page 2-5 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Total System Wattage Capacity WATTAGE Hopper 2500w 2500w 2500w Up to 2 Optional Drop-in Grids 2500w 5000w applicable (2500 w each) Hose + Applicator 1 & 2...
Page 20
Page 2-6 Description ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Wattage Chart D15/D25/D45 The ASUs are available in 12 electrically different versions. The following table shows the wattage and circuit breaker amps for each configuration: 32Amp 30Amp...
Description Page 2-7 ITW Dynatec Revised 11/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Dynamelt D XX V6X X X X X X X X X X DX FX - X X X X X . . . HOPPER SIZE: 15 = 15kg (33 lb)
Installation Page 3-1 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Chapter 3 INSTALLATION Placing the ASU The D15/D25/D45 SERIES ASUs can stand alone on flat surfaces. Access is needed for the main electrical power and the serial communication connections to come in from below the unit and to connect to the V6 Base Module (which is inside the panel box).
Page 3-2 Installation ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Lifting the ASU WARNING The unit must be lifted by two persons, using proper lifting technique, one per- son at either end. Securely hold it under its base plate. No belts or hooks should be used.
Installation Page 3-3 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Installation Note: Re-read Chapter 1 “Safety Precautions” before performing any installation procedures. All installation procedures must be performed by qualified, trained technicians. After the D15/D25/D45 SERIES ASU has been properly mounted, the following general sequence should be followed for installation: 1.
Page 26
Page 3-4 Installation ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 3. A voltage configuration connector (plug), appropriate for your order, has been installed in your ASU. Before proceeding, verify that this plug is correct for your operating voltage.
Page 28
Page 3-6 Installation ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 4. At installation, the customer must make the following terminal connections into the ASU’s main power (ON/OFF) switch and modules. The modules do not need to be removed from the ASU in order to make connections.
Page 3-8 Installation ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 5. The adhesive hoses are connected to the filter manifolds at the back of the machine (see illustra- tion on the next page). On a two or four-hose machine, the hose electrical plugs are connected to the bank of receptacles #1 to 4.
Page 3-10 Installation ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Adjusting the Pressure Relief Valve The function of the pressure relief valve is to protect the gear pump(s) and the pump drive compo- nents from overload and to protect other components from potentially damaging pressure levels.
Page 33
Installation Page 3-11 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 5. Actuate (open) the valves on the applicator(s) in order to fill them with adhesive and purge air from the system. 6. Close the valves (those opened in the last step) to stop the flow of adhesive.
D15/D25/D45 V6 DCL ASU Manual #20-63 Field Installation of Controller Options Customers who choose to modify their adhesive supply unit with ITW Dynatec manufactured options should assure that only qualified technicians perform such installations. The installation of options that require specific procedures and/ or calibration are outlined in this chapter.
Page 35
Installation Page 3-13 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Typical Start-Up and Shut Down of the V6 System Using LCD Controller The following simplified sequence assumes that the LCD HMI DynaControl V6 Controller has been programmed.
Page 36
Page 3-14 Installation ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Typical Start-Up and Shut Down of the Application System Using the Touch Screen The following simplified sequence assumes that the DynaControl Controller has been pro- grammed. Start Up Procedures 1.
Page 37
Installation Page 3-15 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 b. If Pump is in Manual Mode: i. Select the pump for programming under the Settings column on the Pump Overview Screen. ii. Set the manual setpoint value (RPM) under Manual Mode Settings.
Page 3-16 Installation ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Storage and Disposal of the Application System Temporary Storage of the Unit 1. Flush the adhesive application system with flushing fluid (PN L15653), following the instruc- tions detailed in chapter 6 of this manual.
Controller Setup Page 4-1 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Chapter 4 DynaControl V6 CONTROLLER SET-UP Temperature Control Functions in General The DynaControl microprocessor-based proportional temperature control in the ASU performs a number of functions that help to maintain adhesive setpoints in all temperature zones of the DY- NAMELT system.
Page 40
Page 4-2 Controller Setup ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Over-Temperature Setpoint The programmable temperatures that will cause alarms to occur when those temperatures are exceeded. Power is not disconnected, the READY contact opens and the alarm contact opens. If an external alarm has been connected, it will activate.
Controller Setup Page 4-3 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Temperature Zone Enable The temperature zone enable allows the operator to disable unused temperature zones in such a way that they do not appear on the controller’s display and heating is switched OFF.
Page 42
Page 4-4 Controller Setup ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals LCD Error Indication Alarm Display Examples Non‐Active (”solid” (”outlined” Active Zones bar‐graphs) Zones bar‐graphs) Zone has Zone is cold no sensor Zone is at lower tolerance...
Controller Setup Page 4-5 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Touch Screen Error Indication Faults & Alarms If a fault/ alarm occurs, the Acknowledge button (on the Main Screen) and the temperature zone will be highlighted in red. The controller will turn off the internal power to the heaters and an ap- propriate alarm indication will appear in the status line of the controller’s display.
Page 44
Over temperature: hardware over-temperature indication. Communication Error: there is a communication error between the touch panel and controller. Parameter CRC Error: parameter memory has been lost. Call ITW Dynatec Technical Service. Other Faults or Alarms: call ITW Dynatec Technical Service.
Controller Setup Page 4-7 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Settings for a Typical Operation Note: The values given here are approximate settings for a typical packaging application. The val- ues you choose will be based on the type of equipment and adhesive you are using and the nature of your particular operation.
“Actual” temperature indication range: 0C to 260C (32F to 500F). Customer Programmable System Values Preset At The Factory ITW Dynatec can set the controller’s system values to customer’s specs, if provided. If customer’s specs are not provided, the following values will be entered into the DynaControl con- troller at the factory.
Power-On heater start: Yes. Global setpoints: No. Minimum pump speed: 0 RPM). Maximum pump speed: 90 RPM. The ITW Dynatec factory default settings may be re-loaded in the controller per the instructions given in Chapter 5: Zone Configuration (P1 parameter).
Page 4-10 Controller Setup ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals LCD Controller Features One-button Shortcuts Press the “F” buttons to go to: F1 = the Hopper temperature zone F2 = the Hose temperature zone F3 = the first Applicator temperature zone...
LCD Programming Page 5-1 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Chapter 5, Section 1 PROGRAMMING INSTRUCTIONS, V6 LCD FOR D SERIES ASUs DynaControl CONTROLLER, V.6.00 and Up DynaControl (DCL) V6 LCD Interface DynaControl V6 controller technology is available as a liquid crystal display (LCD), which allows an instant overview of temperature zone and pump status, and with a combination Input Wheel/ Enter Knob to facilitate fast programming.
Page 5-2 LCD Programming ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Overview Screen Reference System Status Time of Day Pump Status 7‐Day Scheduler Keypad Status Status Status Line Pump /Motor Zone Speed Bar‐Graph Zone Symbols F1, F2, F3, F4, F5: Toggle “On/Off”...
LCD Programming Page 5-3 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Status Line The status line is the top line of the display. It always lists the System Status, the Time‐of‐Day and the Pump Status. It can also include the status of the Keypad (if locked) and the 7‐Day Scheduler (if active).
Page 5-4 LCD Programming ITW Dynatec Revised 11/14 D SERIES V6 DCL ASU Manuals Bar‐Graphs The temperature status of each zone is shown by a bar‐graph. A solid bar‐graph indicates that the temperature zone is activated. An outlined bar‐graph indicates a temporarily de‐activated temperature zone.
LCD Programming Page 5-5 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Overview Screen Example The Overview Screen illustrated below illustrates an example of a typical system. This melter has two premelt (drop‐in) grids and two hopper heaters for a total of four ASU temperature zones.
Zone names may be re‐programmed to suit the user, but ITW Dynatec's typical D Series zone names are: PREMELT (drop‐in grid), HOPPER, HOSE, HEAD and AUX.
Page 55
LCD Programming Page 5-7 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Selecting Temperature Setpoints After selecting a temperature zone, press the Enter Knob to highlight the setpoint. Turn the In‐ put Wheel to your desired setpoint value. To enter the new value, press the Enter Knob. Contin‐...
Page 5-8 LCD Programming ITW Dynatec Revised 11/14 D SERIES V6 DCL ASU Manuals Pump Screen Return to the Overview Screen if necessary, by pressing the RETURN button. Then press the Pump button (or F5) to go to the Pump Screen.
Page 57
LCD Programming Page 5-9 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals However, to select Manual mode, press the Enter Knob before turning the wheel. Pressing the Enter Knob here toggles between mode selection and RPM selection. Once you are in Manual mode and you have highlighted the RPM selection, turn the Input Wheel to your desired RPM value.
Page 5-10 LCD Programming ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Main Menu Press the Main Menu button on the Overview Screen to go to the following functions: F1: Recipe Management F2: Standby Mode F3: Setpoint Locking F4: 7‐Day Scheduler...
Page 59
LCD Programming Page 5-11 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals To Save a Recipe (SAVE TO PROG): 1. Program the controller as you wish it to be setup for a recipe. Program the following paramet‐ ers: temperature setpoints, zone On/Off settings and motor mode and speed.
2453, press the sequence “F2, F4, F5, F3” (Note: setup an access code on page 3 of the System Configuration Menu). The ASU is shipped from ITW Dynatec with a default access code of “1111”. Keypad is locked,...
Page 61
LCD Programming Page 5-13 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Programming Sequence: Set‐up each Daily Program entirely before moving on to the next Daily Program. Up to three Daily Programs may be setup. All time selections are based on a 24‐hour clock.
Page 62
Page 5-14 LCD Programming ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Daily Program #2: On Fridays, the ASU will Switch‐On at 5:30am. It will go into Standby at 12:30pm. It will come out of Standby at 1:00pm and will Switch‐Off at 4:30pm.
LCD Programming Page 5-15 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Info Menu (F5) The info screens contain details about the hot melt system and can aid in troubleshooting. Info Screen #1: The first Info Screen lists temperature zone and pump configuration. It also provides the revision level of the controller's modules and the elapsed time on the Dynamelt ASU's controller.
Temperature/ Pressure Conversion ‐ Fahrenheit or Celsius/ PSI or BAR Language Selection ‐ English, German, Spanish, French, Chinese or Japanese Zone Configuration ‐ typically configured by ITW Dynatec Pump Configuration ‐ typically configured by ITW Dynatec Setpoint Limitation ‐ sets a limit on the maximum setpoint Hi/Low Tolerance ‐...
Zone Configuration (P1) This menu configures the controller's temperature zones by listing the number of each type of zone. Zone configuration is typically done at the ITW Dynatec factory and does not require pro‐ gramming by the user. The Zone Configuration screen may be used to reload the ITW Dynatec factory default controller parameters.
Page 5-18 LCD Programming ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Setpoint Limitation (P2) This parameter sets the maximum temperature zone setpoint. The setpoint limitation is useful for an adhesive with a low melt temperature. In this case, the maximum selectable setpoint could be lowered in order to avoid over‐heating the adhesive.
LCD Programming Page 5-19 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Standby Temperature Difference In Standby mode, the temperatures of all active temperature zones decrease by a programmed amount and the pump(s) stop pumping adhesive. The programmed decrease in zone temperatures is the standby temperature difference. The standby temperature difference applies to all zones once standby is activated.
Page 5-20 LCD Programming ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals change the function from activate or deactivate. To program the controller to Stop the Pump After Hopper Empty, first press the Configuration button ( ) or F1 to bring up the parameter, then press the Enter Knob to change the function from activate or deactivate.
Main Menu, F3. The Dynamelt ASU is shipped from ITW Dynatec with a default code of 1111. To re‐program the access code, the current access code must be entered. All access codes must be 4‐digit numbers using the digits 1, 2, 3, 4 and 5 only.
Page 5-22 LCD Programming ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Customer Zone Names (P4) With this configuration parameter, the user may personalize the names of the temperature zones with names that are more descriptive for his application. That is, instead of the factory‐set zone names of Z01, Z02, Z03, etc., the customer may prefer temperature zone names such as...
LCD Programming Page 5-23 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Programming the Zone Names NOTE: This feature cannot accommodate Chinese language characters. After selecting the Customer Zone Names parameter and pressing the Enter Knob to display YES, press F3 (Change Text) to begin programming.
Page 5-24 LCD Programming ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Power‐On Configuration (P4) Two start‐up parameters are programmed at the Power‐On Configuration screen, and they are set by choosing YES or NO: Power‐On Motor Stop At the Power‐On Motor Stop parameter, you decide if you prefer that the motor to be stopped when the ASU is turned on (if so, choose YES) or if you prefer that the motor remain in its previ‐...
LCD Programming Page 5-25 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Global Setpoints (P4) Setpoint programming may be simplified by programming Global Setpoints. With this paramet‐ er, the user programs a hopper setpoint and the controller configures all of the other zones.
(solution = replace the motor), b. there may be a faulty motor drive (solution = replace the motor drive), c. there may be a motor overload (contact ITW Dynatec, Technical Service). SYSTEM FAULT ! This fault, seen on the controller display, will result if the V6 modules on the DIN rail are not connec‐...
Page 75
LCD Programming Page 5-27 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals TEMP SENS FAULT PRESS TEMP SENS FAULT PRESS Status Status F5 = Zone Off Advance to the temperature zones display to see which zone is affected. The two status lines shown above will alternate in this mode.
Page 76
Page 5-28 LCD Programming ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals...
ITW Dynatec Programming Page 5-1 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Chapter 5 DYNACONTROL V6 TOUCH PANEL for DYNAMELT M & D ASUs Version 01.2016 Setup Your System's Parameters Program the controller parameters to meet the specific temperature requirements of your production.
Page 78
Page 5-2 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Alphabetic Entry Keypad • Use the alphabetic keypad to enter or change text, e.g. temperature zone names. • In the top window, the temperature zone name will be displayed.
ITW Dynatec Programming Page 5-3 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Main Screen The Main Screen is displayed automatically when the unit is switched ON. The Main Screen provides a comprehensive overview of the status of each of the temperature zones and the system as a whole.
Page 80
Page 5-4 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Main Screen, if six or fewer zones in any column are activated:...
Page 81
ITW Dynatec Programming Page 5-5 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Item Description Status Line Display of the actual status of the unit: • READY = All zones are within their setpoint temperatures and the unit is ready for operation.
Page 82
Page 5-6 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description • The actual values of the temperature zones are displayed in columns under the icons. Zone status is indicated by color: the zone field is colored green when the zone reaches setpoint, yellow while the zone is heating up, grey it it has been temporarily switched off and red if in alarm.
ITW Dynatec Programming Page 5-7 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Temperature Zones Set Screen To go to this screen, press the Set/Act button on the Main Screen. The Set screen allows you to program the setpoint temperature for each activated zone. Each zone requires a temperature setpoint.
Page 84
Page 5-8 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Zone On/Off Switch on the Numeric Entry Keypad Item Description Zone On/Off Switch • Zones can be activated/ deactivated temporarily. Some zones (e.g. Hopper) cannot be deactivated.
ITW Dynatec Programming Page 5-9 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Pump Overview Screen To go to this screen, press the Pumps button on the Main Screen. While on the Pump Overview Screen, all changes are immediate (you do not need to confirm).
Page 86
Page 5-10 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description All Pumps Buttons Press one of the All Pumps buttons (either MANUAL, STOP or AUTO) to set all pumps to the desired function at one time.
Page 87
ITW Dynatec Programming Page 5-11 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Pump Control Screen/ Linear Line Speed To go to this screen, press the Pump 2 field on the Pump Overview screen (to go to the Pump 1, etc.
Page 88
Page 5-12 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description Set the pump to the desired mode by pressing MANUAL, OFF (STOP) or AUTO. • MANUAL: The pump speed is adjusted manually by the operator. If MANUAL is selected the icon is highlighted green.
Page 89
ITW Dynatec Programming Page 5-13 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Extended Pump Mode Settings Screen, Linear Line Speed, Pressure Control To go to this screen, press the Settings button on the Pump Control screen.
Page 90
Page 5-14 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description System 1 Pump 1 is selected. Pump Name Touch the input box and an Alphabetic Entry Keypad will appear. Enter your desired pump name and confirm by pressing OK.
Page 91
ITW Dynatec Programming Page 5-15 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Pump Control/ Pressure Control Screen To go to this screen, press the Pump 2 field on the Pump Overview screen (to get to the Pump 1, etc.
Page 92
Page 5-16 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description Switch Point (if in Auto Mode only) Switch Point is set at a percentage of line speed. In the example shown above, 10%L equals 10% of line speed.
Page 93
ITW Dynatec Programming Page 5-17 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Automatic Ramp Compensation To go to this screen, press the Automatic Ramp Compensation button on the Extended Pump Mode Settings Linear Line Speed screen.
Page 94
Page 5-18 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Ramp Compensation allows tuning of adhesive amounts during acceleration and deceleration of main machine to reduce waste and increase machine efficiency by entering appropriate parameters.
ITW Dynatec Programming Page 5-19 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Control Switch On/Off and Standby Switch To go to this screen, press the Control button on the Main Screen. This screen allows you to turn the system On or Off and to activate/deactivate standby condition.
Page 96
Page 5-20 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description Standby Switch • Press the Standby switch to activate or deactivate the standby condition. When Standby is activated, the button will be highlighted blue.
ITW Dynatec Programming Page 5-21 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Systems Screen To go to this screen, press the Systems button on the Main Screen. This screen displays all attached systems and allows you to select the desired system to control ...
Page 98
Page 5-22 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description System # Button • Each system is assigned with a number. • Press the desired number to go to the appropriate system to control and to edit its parameters.
ITW Dynatec Programming Page 5-23 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Settings Screen To go to this screen, press the Settings button on the Main Screen. This screen allows you to set the parameters displayed: Language, Temperature/ Pressure Units,...
Page 5-24 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Heating Priority Screen To go to this screen, press the Heating Priority button on the Settings Screen. This screen allows you to set a Heating Priority for each zone. Heating Priority allows the hopper zones to heat to their ready temperatures before the other zones begin heating.
Page 101
ITW Dynatec Programming Page 5-25 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Zone Configuration Screen To go to this screen, press the Zone Configuration button on the Settings Screen. This screen allows you to enter zone names and to set Offset Temperature and other Control Settings for each zone.
Page 102
Page 5-26 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Zone Settings To go to this screen, press a zone input box on the Zone Configuration Screen. Item Description Zone Name Touch the input box and an Alphabetic Entry Keypad will appear. Enter your desired name and confirm by pressing OK.
Page 103
ITW Dynatec Programming Page 5-27 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Item Description Use Temperature Integration • Depending on your Temp Module this function can be activated/ deactivated. • If you experience strong variations in actual temperature read-out, an integration function can be activated to eliminate EMC influence.
Page 5-28 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Fieldbus Setup Screen To go to this screen, press the Fieldbus Settings button on the Settings Screen. When communicating to a parent machine which utilizes profibus or EtherNet IP, the unit must have a Fieldbus Address to identify it.
ITW Dynatec Programming Page 5-29 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 General Settings Screen To go to this screen, press the General Settings button on the Settings Screen. This screen allows you to set the parameters shown across the screen’s top line (Item #1, shown below).
Page 106
Page 5-30 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description Temperature Alarm Window • This is the programmable temperature range which allows the unit to go into Ready condition. The Temperature Alarm Window is a deviation (e.g. ± 20°C / 36°F) from the setpoint.
ITW Dynatec Programming Page 5-31 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Standby Settings To go to this screen, press the General Settings button on the Settings Screen. Item Description Parameter Selection tabs The Standby Settings tab has been selected.
Page 108
Page 5-32 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description Press the left-pointing arrow to go to the previous General Settings screen. Press the right-pointing arrow to go to the next General Settings screen.
ITW Dynatec Programming Page 5-33 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Level Control Settings To go to this screen, press the General Settings button on the Settings Screen. If Digital Level Sensor is installed:...
Page 110
Page 5-34 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs If Analog Level Sensor is installed: Item Description Parameter Selection tabs The Level Control Settings tab has been selected. Empty Level If fill level is lower than this parameter an empty message will be generated.
ITW Dynatec Programming Page 5-35 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Pressure Zero Calibration To go to this screen, press the General Settings button on the Settings Screen. Item Description Parameter Selection tabs The Pressure Zero Calibration tab has been selected.
Page 5-36 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Calibrating Screen Item Description Parameter Selection tabs The Pressure Zero Calibration tab has been selected. Pressure Zero Calibration If (optional) pressure sensors are installed on the unit, the pumps can be pressure controlled.
6. Activate the names by pressing “Activate Customer Zone Names”. Later you may deactivate (or re-activate) the names by pressing “Activate Customer Zone Names” again. When personalized names are deactivated, the ITW Dynatec default zones names become active. You may also press Erase Zone Names to delete your loaded zone names and you may load...
Page 114
Page 5-38 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Item Description Result A message will confirm if the names were successfully loaded, activated or deactivated, or if there was an error in loading the names.
Page 115
Parameter Selection tabs The Support tab has been selected. If requested by ITW Dynatec Support you can insert USB Flash Drive to create a system dump file. This file can be send to ITW Dynatec for offline diagnostics. Press the left-pointing arrow to go to the previous General Settings screen.
Page 5-40 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Recipes Screen To go to this screen, press the Recipes button on the Settings Screen. This screen allows you to create recipes (or “programs”). A recipe is a set of temperature set points and parameters which the user has programmed and stored in the controller for future use.
Page 117
ITW Dynatec Programming Page 5-41 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Item Description BACK Button Press to return to the previous screen. Restore Recipes This button is visible only if USB Flash Drive is inserted into the Touch Panel.
Page 5-42 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Time & Scheduler Screen To go to this screen, press the Time & Scheduler button on the Settings Screen. This screen allows you to set the current date and time, and program the scheduler.
Page 119
ITW Dynatec Programming Page 5-43 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Item Description Programming • Select a timer for programming by pressing Timer 1, Timer 2 or Timer 3. • Select either System On/Off or Standby On/Off.
Page 120
Page 5-44 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Example: The display on the right shows that Timer 3 is not programmed and not activated:...
ITW Dynatec Programming Page 5-45 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Log Book Screen To go to this screen, press the Log Book button on the Settings Screen. The Log Book provides a read‐only history of the last 100 (maximum) controller faults and events.
Page 5-46 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Security Screen To go to this screen, press the Security button on the Settings Screen. This screen allows you to set securities (with password) for access and for changing parameters.
Page 123
ITW Dynatec Programming Page 5-47 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Item Description Section Access Press the buttons to select access to each parameter as follows: • Unlock = the parameter may be changed by all users.
Page 5-48 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs System Info Screen To go to this screen, press the System Info button on the Settings Screen. This screen displays information about the V6 controller and its modules. The screen is read-only.
To go to this screen, press the Licenses button on the System Info Screen. To purchase licenses with additional features, please contact ITW Dynatec Customer Service and provide your unit’s serial number (provided on this screen). You will receive an USB Flash Drive with the license.
Page 126
Page 5-50 ITW Dynatec Revised 1/16 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Software Licenses To go to this screen, press the Software Licenses button on the License Management Screen. Item Description Display Software Licenses Click on Entry for detailed license information.
ITW Dynatec Programming Page 5-51 V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16 Acknowledge Button The Acknowledge Button is on the Main Screen & Temperature Zones Set Screen. 1: no faults or alarms indicated...
• Communication Error = Communication error between the touch panel and controller. • Parameter CRC Error = parameter memory is lost. Call ITW Dynatec Technical Service. • Other Faults or Alarms = Call ITW Dynatec Technical Service. When an alarm condition occurs, the current display will be interrupted only if a sensor (or motor drive) failure occurs.
Maintenance Page 6-1 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Chapter 6 PREVENTIVE MAINTENANCE Note: Re-read Chapter 1 “Safety Precautions” before performing any maintenance procedures. All maintenance procedures must be performed by qualified, trained technicians. General Cleaning The D15/D25/D45 SERIES ASU enclosure is finished with an extremely durable polyurethane paint.
Maintenance Page 6-3 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Primary Filter Cleaning See the illustration below for location of the primary filter. 1. Pump all the adhesive out of the hopper. 2. Lower the temperature of the application system to the adhesive’s softening point.
Page 6-4 Maintenance ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Pump Shaft Leak There is a cutout in the base plate, directly below the pump Seal Assembly shaft, which will allow adhesive from a leaking pump to exit the ASU.
Maintenance Page 6-5 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Purging the Filter Manifold (Output Filter) of Adhesive and Pressure As a safety precaution, the ASU’s system should be purged of pressure and adhesive before at- tempting to change the output filter or before removing any of the hoses or applicators from their manifold port.
Page 134
Page 6-6 Maintenance ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 2. Reduce the ASU’s pump pressure to zero. Note: the hose used in the following process is merely for the convenience of depositing flushing fluid. This procedure does not have to be repeated for each hose in the system.
HOT SURFACE HIGH VOLTAGE ITW Dynatec systems use electrical power that can be life threatening and hot-melt adhesives that can cause serious burns. Re-read Chapter 1 “Safety Precautions” before performing any troubleshooting or repair procedures. All troubleshooting and repair procedures must be per- formed by qualified, trained technicians.
The normal life of this battery is about ten years. When the battery needs replacement, the scheduler’s clock does not function, but other controller features remain intact. Re- turn the board to ITW Dynatec for battery replacement. DynaControl V6 Modules The DynaControl V6 control package is built from encapsulated modules that snap onto the DIN rail within the ASU.
Page 138
Page 7-4 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Handling Modules and Printed Circuit Boards (PCBs) The Dynamelt ASU and DynaControl controller utilize several printed circuit boards (PCBs). These boards are extremely sensitive to electrostatic charges. When working near or with any PCBs, the following procedures must be followed to avoid damage to them.
Page 139
The V6 Base Module is the main control module of the DynaControl V6 controller. Most of the in- ternal and external components are connected to the Base module. The Base module is always the top (first) module on the DIN-rail. ITW Dynatec recommends using dry contacts for connecting to DynaControl V6! cont.
Page 7-6 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals V6 Base Module, cont. Description of Components The following items are referenced to the illustration on page 7-5: Item #1 The controller runs on standard 24VDC. The supply voltage, coming from the 24VDC power supply, is connected to this terminal.
Page 141
Troubleshooting Page 7-7 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals V6 Base Module, cont. Alternatively it is possible to use the external inputs via ‘dry’ contacts: WARNING: The ASU’s internal 24VDC is grounded. It is not recommended to connect external 24VDC with the internal.
Page 142
Page 7-8 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals V6 Base Module, cont. Item #8 This connects to the motor driver. MB / MC: Alarm contact indicating driver fault (N.C.) SC / S1: Pump start signal...
Troubleshooting Page 7-9 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals V6 Temperature Module PN 115735 The V6 TEMP module(s) is mounted next to the V6 Base Module on the Din-rail. It requires 24VDC supply voltage. It is responsible for the temperature control of all heated temperature zones.
Page 144
Page 7-10 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals V6 Power Module PN 115732 The V6 POWER module provides controlled power to the heater of the first five zones. It receives its control signals from the V6 TEMP module. The Power Module also has protected outputs for the DC power supply and motor drive.
Troubleshooting Page 7-11 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals V6 Power Module, cont. Fuses The fuses of the POWER Module are located underneath a protective cover. The cover should only be removed after the ASU is switched Off and disconnected from the main power supply. After checking or replacing fuses, the cover must be re-installed.
Page 146
Page 7-12 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals V6 Aux Power Module PN 115733 The V6 AUX module provides controlled power to the heater of the additional five zones. It re- ceives its control signals from the V6 TEMP module. There are two of these modules on a D Series ASU.
Troubleshooting Page 7-13 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals V6 Motor Module PN 116823 A maximum of two V6 MOTOR modules may be installed on the ASU. Each motor module con- trols up to four motors. Each motor control output is associated with an enable contact and an en- coder input.
Page 148
Page 7-14 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals...
Troubleshooting Page 7-15 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Optional Printed Circuit Boards Wiring diagrams and other details on the following optional PCBs can be found on the main ASU schematic in Chapter 11: Adhesive Level Sensor (hopper low level detection)
Page 7-16 Troubleshooting ITW Dynatec Revised 11/14 D SERIES V6 DCL ASU Manuals Optional V6 BUS Communications Module PN 117382 The V6 BUS module is used with a communications protocol ad- apter to provide functionality so that the ASU may be operated remotely.
Page 151
Troubleshooting Page 7-17 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Temperature Resistance in Ohms Hose Length Resistance Meters Feet in Ohms 466-544 279-326 236-275 189-221 155-181 118-137 77-90 Nominal Hose Heater Resistance for #6 DynaFlex Hoses...
Page 7-18 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Error Indication Alarm Troubleshooting Guide The operation of error indication alarms is described in Chapter 4. When checking for correct equipment operation in the following guide, be aware that all heaters will go off immediately after an error indication alarm occurs if the operator takes no action.
Page 153
Troubleshooting Page 7-19 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Problem Possible Cause Solution Hopper Sensor Open 1. Sensor cable has become 1. Verify that hopper sensor cable is unplugged from V6 properly connected at X3 on the Temperature Module.
Page 154
Page 7-20 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Solution Problem Possible Cause 1. Inspect hopper heater wiring for Hopper Heater Open 1. Disconnection in hopper proper connections. heater circuit. 2. Verify that all connections are 2.
Page 155
Troubleshooting Page 7-21 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Problem Possible Cause Solution (Optional) Drop-In Grid 1. Sensor cable has become 1. Verify that grid sensor cable is Sensor Open unplugged from the Tem- properly connected at X3 (or X2) on the perature Module.
Page 156
Page 7-22 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Problem Possible Cause Solution (Optional) Drop-in Grid 1. Disconnection in grid’s 1. Inspect grid’s heater wiring for Heater Open heater circuit. proper connections on AUX Power PCB.
Page 157
Troubleshooting Page 7-23 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Solution Problem Possible Cause 1. Re-program tolerance setpoint to allow Hose/ Head 1. Hose/ Head tolerance (hi/ a larger deviation. (No.) Overtemp low limits) incorrectly programmed. 2.If a hose or head status LED on the 2.
Page 158
Page 7-24 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Problem Possible Cause Solution Hose/ Head (No.)* Not 1. Disconnection between 1. Visually examine connector for proper Heating hose and ASU. contact and seating. If pins or housings...
Page 159
Troubleshooting Page 7-25 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Solution Problem Possible Cause Hose/ Head (No.)* 1. Disconnection between 1. Visually examine affected hose/ head- Not Heating hose/ head and ASU. plug and ASU socket for cleanliness and (Heater Circuit Open) proper contact and seating.
Page 160
Page 7-26 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Solution Problem Possible Cause 1. Re-program tolerance to allow a Aux (No.) Overtemp 1. Aux tolerance (hi/ low) larger deviation. setpoints incorrectly programmed. 2. Use a clamp-on ammeter to monitor 2.
Page 161
Troubleshooting Page 7-27 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Solution Problem Possible Cause Aux (No.) Sensor 1. Disconnection between 1. Visually examine connector for proper- Open Aux connector and ASU. contact and seating. If pins or housings are damaged, repair or replace Aux har- ness (in ASU).
Page 162
Page 7-28 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Solution Problem Possible Cause Aux (No.) Heater 1. Disconnection between 1. Visually examine affected Aux plug Open Aux and ASU. and ASU socket for cleanliness and prop- er contact and seating.
Troubleshooting Page 7-29 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Adjustable Adhesive Pressure Relief Valve D Series ASUs are outfitted with a high-pressure relief valve located on the outlet filter manifold. The valve is adjustable and it does not affect adhesive pressure under normal operating conditions.
Page 7-30 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Operation of the ASU’s Gear Pump Manual or Automatic Pump Operation Choose MANUAL, STOP or AUTO gear pump operation via the PUMP button on the DynaCon- trol Overview screen. When the Dynamelt’s pump is to be operated manually (that is, without a line following signal), the manual mode is used to control pump speed (and adhesive output).
Troubleshooting Page 7-31 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Troubleshooting the ASU Pump No special tools are needed for working on the ASU pump. See Chapter 8 of this manual for dis- assembly/ assembly procedures for the ASU pump, and Chapter 10 for locating pump parts on the component illustrations (exploded-view drawings).
Page 7-32 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Gear Pump Troubleshooting Guide WARNING HOT SURFACE & ADHESIVE Some of the procedures in the following Troubleshooting Guide require working near hot adhesive. Be sure to wear protective gloves, safety glasses and clothing and use proper tools for handling hot melt components.
Page 167
Troubleshooting Page 7-33 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Solution Problem Possible Cause 1. Check parent machine. Pump doesn’t operate 1. Parent machine is not in “Auto” mode, running. hopper is at Ready 2. Re-program pump.
Page 168
Page 7-34 Troubleshooting ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Solution Problem Possible Cause 1. Remove seal and bearing from pump. Adhesive leak at pump 1. Pump seal is incorrectly Verify that all components are shaft seal.
Page 8-2 Disassembly ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 To Access the Electrical Components (See illustrations on pages 4 thru 7 in Chapter 10) Verify again that the main power is OFF. Open the front (panel box) door.
Disassembly Page 8-3 ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Opening Modules There are various electrical components located within the modules. To open a module, use two fin- gers to pull straight up on the top (lid) of the module. Position your fingers toward the outside edge (not the center) of the module.
Page 8-4 Disassembly ITW Dynatec Revised 10/14 D15/D25/D45 V6 DCL ASU Manual #20-63 Pump O-ring Replacement: 1. Remove the pump from the ASU (see instructions on Pump Pump O-ring previous page). 2. Remove the external pump seal from its groove on the back of the pump.
Options Page 9-1 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Chapter 9 AVAILABLE OPTIONS & ACCESSORIES Pressure Gauge Kit: PN 101175 An optional analog pressure gauge can be mounted on the outlet filter manifold. Reading the adhe- sive pressure at the manifold, rather than in-line on a hose, allows for more precise monitoring of system pressure.
Page 9-2 Options ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Pump Options Gear Pumps For higher tolerances and precision, several gear pumps are available for the ASU. Gear pumps give better service for continuous applications or applications which require more control over the volume of adhesive pumped.
Options Page 9-3 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals DynaControl V6 Options HMI Selection LCD Controller PN 115719 The LCD (liquid crystal display) controller is available with the complete line of DynaControl fea- tures. It features an intuitive, multi-line, graphic display and operates via an input wheel Touch Screen Controller PN 118135 The V6 color touch screen controller is available with an expanded line of DynaControl features.
Note: most common nuts, bolts and fasteners can be obtained locally at your hardware store. Spe- cialty fasteners are available by contacting ITW Dynatec’s Customer Service.
Page 191
ITW Dynatec Component Illustrations Page 10-15 D15/D25/D45 V6 DCL ASU Manual #20-63 Revised 10/14 Pump # 100860 has one bearing in this shaft Pump # 100861 has two bearing in this shaft Pump # 100861 has two bearing in this shaft Pump # 100860 has one bearing in this shaft PN 100860 &...
Schematics Page 11-1 ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals Chapter 11 SYSTEM SCHEMATICS & ENGINEERING DRAWINGS Notes: 1. ALL WIRE MIL-W-22759/10 OR 12, MINIMUM 600 VOLTS, 260 DEG. C 2. SOLENOID(S) VOLTAGE AND TIMING METHOD DEPENDS ON APPLICATION.
Page 206
Page 11-2 Schematics ITW Dynatec Revised 10/14 D SERIES V6 DCL ASU Manuals HOSE SCHEMATIC PN 101082 REV. G ASU to Applicator...
Page 216
118521 AUX RECEPTACLES AWG16 AWG12 AWG10 AWG16 AWG10 HOSE & HEAD MOTOR CABLES NOTE: IF MORE THAN ONE WIRE IS CONNECTED TO ONE TERMINAL OF THE GROUND BAR, THOSE WIRES HAVE TO BE CRIMPED TOGETHER IN ONE APPROPRIATE FERRULE. D15/25/45 V6 ALL GROUND WIRE HAVE TO BE YELLOW/GREEN.
Page 217
118521 LINE SPEED POWER SUPPLY G : V L : mA 24VDC / 2A +24V ETHERNET PUMP #2 N30.2 +24V L30.2 9 10 -A60.0 RELAY OUTPUT POWER -A60.1 -A60.5 V6-BASE4 -A70.6 SUPPLY V6-MOTOR 24VDC / 2A V6-TEMP16 INPUT MB MC MB MC S1 A1 FIELD BUS...
Page 218
118521 REFERENCE DESCRIPTION MANUFACTURER / PN REFERENCE DESCRIPTION MANUFACTURER / PN TERMINAL BLOCK, POWER ENTRY -A20.2 Y-CAP ASSEMBLY -Q20.1 MAIN SWITCH / CIRCUIT BREAKER 32A / 63A 600V -A30.0 POWER PCB 115732 -A50.0 DC POWER SUPPLY -XS40.0 CONNECTOR, FEMALE SOCKET, 13+PE -XS40.2 -XS40.3...
General Description ITW Dynatec’s metering gear pumps are manufactured to precise tolerances. To retain their high performance, these pumps must be carefully installed and maintained. These pumps are CE (Declaration of Conformity) rated.
Page 220
• Installation, operation, and maintenance instructions must be correctly and strictly followed, otherwise, injury to personnel or serious damage to the pump could result. • ITW Dynatec cannot accept responsibility for unsatisfactory performance or damage resulting from failure to comply with instructions.
Page 221
ITW Dynatec Page 3 Appendix Pumps Rev.10.15 Installation WARNING • Follow all General Safety Instructions. • Ensure pump is free from protective packing materials and rotates freely. • Only use the pump as intended, while remaining aware of safety risks, and in adherence to the instructions in this manual.
Page 222
Pump inlet pressure is an important feature for lubrication and fluid stability. Materials for pump construction are important for corrosion and wear resistance. Consult ITW Dynatec for detailed applications. Normally the pumps are single or dual output. Typical speed ranges are 10-90 rev/ min.
Page 223
• Under normal operating conditions, the airborne noise level will be less than or equal to 70 dB. • If airborne noise levels above 70 dB are noted, the pump is not operating under normal conditions or component failure is imminent. Contact your ITW Dynatec representative for assistance.
Page 224
UNC and BSF threads. Multiply by 0.8 for BSVV threads (multiply by 0.67 for stainless steel). ITW Dynatec frequently provides special features at their customer’s request. Please consult with ITW Dynatec, quoting job and pump references, if questions arise. Maintenance Notes WARNING •...
Page 225
ITW Dynatec Page 7 Appendix Pumps Rev.10.15 Pump shaft Leakage If shaft seal leakage is present the seal should be replaced. If the pump uses Packing seals: WARNING • Slight leakage is necessary to lubricate the packing. • If not appropriately collected, packing leakage may make floor slippery and/or expose personnel to hazardous fluids.
Page 226
Check process conditions for proper changed. melt temperature, pressures, viscosities and materials. 4. Foreign particle. Send pump for repair to ITW Dynatec. 5. Possible internal Send pump for repair to ITW Dynatec. damages. Excessive seal assembly 1. Worn seal plate.
Page 227
Page 9 Appendix Pumps Rev.10.15 Reconditioning Should reconditioning (overhauling) become necessary, return the pump to ITW Dynatec. Pump Shaft Seal Replacement The ITW Part Number for all Tool Steel High Accuracy Pump Shaft Seals (8.5cc and smaller) is PN 807729.
Page 228
Page 10 ITW Dynatec Rev.10.15 Appendix Pumps Transport / Storage DANGER • Death or crushing of limbs caused by falling or overturning loads! • Bodily harm can occur if excessive weight is lifted or moved incorrectly! • Protection from hot surfaces and hot liquids must be provided by the operator! Take care not to drop the pump.
ITW Dynatec Seite 1 Appendix Signal Isolator Rev.6.15 Signal Isolator, V6, PN 117143 General Description The isolated converter DAT 4531 D is able to measure voltage and current signals. In function of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy and performance stability both versus time and temperature.
Page 230
Seite 2 ITW Dynatec Rev.6.15 Appendix Signal Isolator Programming Configuration by DIP-Switches 1) Open the suitable door on the side of the device. Refer to TAB.1. 2) Set the input type by the dip-switch SW1 [1..4]. 3) Set the output type by the dip-switch SW1 [6..8].
OIL FILLED MELT PRESSURE TRANSMITTERS Output 4...20mA WE SERIES Pressure Transducer PN 812340 The WE series of Gefran, are pressure transmitters for using in High temperature environment. The main characteristic of this series is the capability to read temperature of the media up to 315°C. The constructive principle is based on the hydraulic tra- smission of the pressure.
Page 233
ELECTRICAL CONNECTIONS EXTERNAL MAGNETIC CURRENT OUTPUT (4...20mA, two wires) AUTOZERO AUTOZERO 6-pin 8-pin 6-pin 8-pin Supply voltage Supply voltage CONTROLLER (10...30Vdc) (10...30Vdc) n.c. n.c. Signal Signal (4...20mA) (4...20mA) n.c. n.c. AMPL./CONV. Calibration shunt Autozero E - F E - F E - F E - F G - H...
Page 234
ORDER CODE 000= Standard version Autocompensation (*) Special or customized versions Standard available on request (*) available for ranges > to 100bar External autozero (*) not available for WE3 version Magnetic autozero FLEXIBLE LENGTH OUTPUT SIGNAL (mm / inches) 4...20mA Standard (WE0) CONFIGURATION none...
Need help?
Do you have a question about the DYNAMELT D15 Series and is the answer not in the manual?
Questions and answers