Restoring Communication - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

Section 9
Troubleshooting
Table 184:
Behavior during IRF in SIM8F module
Module IRF
IRF in SIM8F module
9.2
280
RIO600 as a whole
Continues normal function with
corrective action
Table 185:
Behavior during IRF in SIM4F module
Module IRF
RIO600 as a whole
IRF in SIM4F module
Continues normal
function with corrective
action

Restoring communication

1.
Check the firewall configuration in the host PC. A firewall may prevent the FTP
and ping command from working.
2.
Open the TCP/IP and UDP ports by adjusting the firewall settings.
Behavior in an IRF condition
LECM
1.
Shows IRF by steady IRF
LED on LECM module
2.
Shows IRF source
information on WHMI
under faults page
3.
SIM8F module information
is sent with bad quality
4.
GOOSE: Updates quality
of all modules' data
attributes and RIO600
module health as per IEC
61850
5.
Opens DOM4 IRF output
contact, if it is configured
Behavior in an IRF condition
LECM
1.
Shows IRF by
steady IRF LED
on LECM module
2.
Shows IRF
source
information on
WHMI under
faults page
3.
SIM4F module
information is
sent with bad
quality
4.
GOOSE:
Updates quality
of all modules'
data attributes
and RIO600
module health as
per IEC 61850
5.
Opens DOM4
IRF output
contact, if it is
configured
1MRS757488 H
DIM8L/DIM8H, DOM4, RTD4,
AOM4
1.
Continues normal
operation
2.
Shows error in previous
module over LECM WHMI
(if detected)
DIM8L/DIM8H, DOM4,
RTD4, AOM4
1.
Continues normal
operation
2.
Shows error in
previous module
over LECM
WHMI (if
detected)
Installation and Commissioning Manual