1MRS757488 H
Section 6
6.1
6.1.1
Table 20:
Operating parameter settings for LECM
Parameter name
Range
General Parameters
Test Mode
Standalone configuration
Communication
IP Address
Subnet Mask
Default Gateway
Synch Source
IP SNTP Primary
Table continues on next page
RIO600
Installation and Commissioning Manual
Commissioning

Parameter setting

The operating parameters of the LECM, DIM8H, DIM8L,DOM4, RTD4, AOM4,
SIM8F and SIM4F modules.

Operating parameter settings LECM

Unit
Disable/Enable
False/True
None/SNTP/Modbus
Default value
Description
Disable
This parameter enables or disables the
mode parameter in RIO600.
False
If enabled, RIO600 operates in standalone mode
without any GOOSE/Modbus commands
192.168.2.10
IP address for RIO600
255.255.255.0
Subnet mask address for RIO600
192.168.2.1
Gateway address for RIO600
None
Time synchronization (SNTP) selection.
None: SNTP functionality not selected. If the
SNTP time synchronization is not required or
available, the
set to "None". RIO600 displays the default time on
the WHMI in red to indicate that time is not
synchronized.
SNTP: SNTP functionality selected. If two
separate SNTP servers are available, their IP
addresses can be configured with parameters
SNTP Primary and IP SNTP Secondary . If a
single SNTP server is used, its IP address can be
configured in the
and the
IP SNTP Secondary parameter can be
configured as "0.0.0.0".
Modbus: Syncronization by unsigned 16 bit UTC
time.
10.58.125.165
IP address for SNTP server 1
Section 6
Commissioning
Test
Synch Source parameter must be
IP SNTP Primary parameter,
IP
57