ABB Remote I/O RIO600 Installation And Commissioning Manual page 169

Table of Contents

Advertisement

1MRS757488 H
Parameter name
Range
Oscillation Time
Description
Channel 1 Inversion
Channel 2 Inversion
Channel 3 Inversion
Channel 4 Inversion
Output channels
Description
RIO600
Installation and Commissioning Manual
Unit
0...4095
ms
Non-inverted/inverted
Non-inverted/inverted
Non-inverted/inverted
Non-inverted/inverted
Interlocking rules for motor driven switch (earthing switch,
disconnector)
When configured for motor driven switch control, the smart control module runs on
different interlocking rules which helps the switchgear to function safely. It checks
different stages of the motor based on different input signals and controls the operation
of the motor. The panel and substation interlocking has to be handled by the connected
protection and control device.
RIO600 ignores commands to operate the motor to its current position. For example,
if the Disconnector is in the OPEN position when RIO600 receives an OPEN
command, no motor operation is performed and the command is ignored.
Commissioning
Default value
Description
4095
This parameter is the
oscillation suppression
time limit. The parameter
value acts as the time
window for the oscillation
detection in ms.
0 means that no
oscillation suppression is
active.
Digital Input 1...4
User defined channel
name not exceeding 30
characters
Non Inverted
channel 1 input type: non-
inverted/inverted
Non Inverted
channel 2 input type: non-
inverted/inverted
Non Inverted
channel 3 input type: non-
inverted/inverted
Non Inverted
channel 4 input type: non-
inverted/inverted
High speed output 1..4
User defined channel
name not exceeding 30
characters
Section 6