Section 6
Commissioning
6.1.4
Table 24:
Operating parameter settings
Parameter name
Range
Description
Input mode
All the below parameters depend on the selected input mode (RTD/mA)
Conn Type
Input Max
Input Min
SuperVision time
Tolerance Low
Tolerance High
Table continues on next page
62
Certain parameters, for example, signal type, inversion and disabling,
are not applicable to the channel that is configured for the IRF
operation. OR logic function should not be used with the contact used
for IRF operation.

Operating parameter settings of RTD/mA module

Unit
Pt100
Pt250
Ni100
Ni120
Ni250
0...20mA
Not in Use
Input mode
Input
- RTD
mode - mA
2-wire
3-wire
-40...200 °
0.0...20.0
C
mA
-40...200 °
0.0...20.0
C
mA
0...5
s
0...4
%
0...4
%
Default value
Description
Analog Input 1...4
User defined channel name not exceeding 30
characters
Not in use
Input channel type selection.
"Not in Use" indicates that the channel is
disabled.
Connection type based on the selected input
mode.
Maximum range of input based on the selected
input mode.
For example, if the selected input mode is "0...20
mA" and the channel has to be configured for
4...20 mA,
Minimum range of input based on the selected
input mode.
For example, if the selected Input Mode is "0...20
mA" and the channel has to be configured for
4...20 mA,
5
The rate at which value of measurements is
reported.
0
Tolerance in percentage on lower value of mA
input range. For RTD, this is not applicable.
For example, if the channel is configured for 4 to
20 mA and selected
(= 0.64) of range (= 16 mA) is applied to
Value . Thus, if measured value is less than Input
Min by Tolerance Low % (= 3.36) of configured
Input Max – Input Min ), the value is
range (
considered "out of range".
0
Tolerance in percentage on higher value of mA
input range. For RTD, this is not applicable.
For example, if the channels are configured for
4...20 mA and selected
4% (= 0.64) of range (= 16 mA) is applied to
Max Value . Thus, if measured value is more than
Input Max by Tolerance High % (= 20. 64) of
configured range (
value is considered "out of range".
1MRS757488 H
Input Max is 20.0.
Input Min is 4.0.
Tolerance Low is 4, then 4%
Tolerance High is 4, then
Input Max – Input Min ), the
Installation and Commissioning Manual
Input Min
Input
RIO600