Description
Fault pass indicator
Operating range
Accuracy
Three-phase inrush
Operating range
detector
Accuracy
Negative-sequence
Operating range
overcurrent protection
Accuracy
Table 197:
Binary inputs (SCM)
Description
Rated voltage
Operating voltage range
Current drain
Power consumption/input
channel
Threshold voltage
Reaction time
Table 198:
High-speed outputs (SCM)
Description
Operating time
Rated voltage
Continuous current carry
Short time current carry
Value
1...100 A (earth-fault and residual current)
10...100 A (instantaneous current)
Depending on the nominal frequency of the
current measured: f
Current:
±1.5% of the set value
Start time :±1.0% of the set value or ±70 ms
Operate time: ±1.0% of the set value or ±30 ms
5...100% Ratio I2f/I1f measurement
Depending on the nominal frequency of the
current measured: f
Current:
±1.5% of the set value or ±0.02 A
Ratio I2f/I1f measurement:
±5.0% of the set value
Operate time: ±35 ms
4...200 A (isolated/compensated network)
200...1000 A (solidly grounded/low-impedance
network)
Depending on the nominal frequency of the
current measured: f = f
Current:
±1.5% of the set value or ±0.02 A
I
= 2 × set value = <36 ms
Fault
I
= 10 × set value = <30 ms
Fault
Operate time: ±1.0% of the set value or ±20 ms
SCM8H
110...250 V DC
±20% of rated voltage
3...3.7 mA
330...925 mW
78 V DC
5 ms...4.0 s filtering time
SCM8H
<1 ms
110..250 V DC
20 A
100 A for 10 ms
Section 10
Technical data
n
n
n
SCM8L
24, 30, 48, 60 V DC
±20% of rated voltage
2 mA
30...130 mW
13 V DC
5 ms...4.0 s filtering time
SCM8L
<1 ms
24, 30, 48, 60 V DC
20 A
200 A for 10 ms
291