ABB Remote I/O RIO600 Installation And Commissioning Manual page 107

Table of Contents

Advertisement

1MRS757488 H
Table 67:
DPHPTOC Settings
Name
Values (Range)
Operation
Off
On
No. of Start Phases
1 out of 3
2 out of 3
3 out of 3
Start Value
50...2000
Operate Delay Time
40...60000
Directional Mode
Forward
Reverse
Non-directional
Characteristics
-179...180
Angle
Max Forward Angle
0...90
Max Reverse Angle
0...90
Min Forward Angle
0...90
Min Reverse Angle
0...90
Min Operate Current
-
Table continues on next page
RIO600
Installation and Commissioning Manual
Name
OpRev
Str general
Str phsA
Str phsB
Str phsC
Str dirGeneral
Str dirPhsA
Str dirPhsB
Str dirPhsC
Settings
Unit
-
-
A
ms
-
Deg
Deg
Deg
Deg
Deg
A
Type
Boolean
Boolean
Boolean
Boolean
Boolean
Integer
Integer
Integer
Integer
Step
Default
-
On
-
1 out of 3
10
480
10
40
-
Forward
1
0
1
80
1
80
1
80
1
80
-
50
Section 6
Commissioning
Description
Operate signal indicating fault in
reverse direction when
Directional mode is set to "Non
Directional".
General start signal
Start signal for phase A
Start signal for phase B
Start signal for phase C
General detected fault direction
Detected fault direction for
phase A
Detected fault direction for
phase B
Detected fault direction for
phase C
Description
Operation Off/On
Number of phases
required for operate
activation
Start value for
overcurrent fault
detection
Operate delay time
Directional mode
Characteristics
angle
Maximum phase
angle in forward
direction
Maximum phase
angle in reverse
direction
Minimum phase
angle in forward
direction
Minimum phase
angle in reverse
direction
Minimum operating
current to allow
directional criteria
99