ABB Remote I/O RIO600 Installation And Commissioning Manual page 156

Table of Contents

Advertisement

Section 6
Commissioning
Parameter name
Phase A
Current
Amplitude
Current Phase
Phase B
Current
Amplitude
Current Phase
Phase C
Current
Amplitude
Current Phase
Residual
Current
Amplitude
Current Phase
LED reset time delay
Fault Indication Reset Method
Update interval for Metering values
148
Range
Unit
0.7000...1.3000
-
-3.0000...
deg
+3.0000
0.7000...1.3000
-
-3.0000...
deg
+3.0000
0.7000...1.3000
-
-3.0000...
deg
+3.0000
0.7000...1.3000
-
-3.0000...
deg
+3.0000
1...1440
min
Self Reset
-
Method
Definite Time
1...15
-
Step
Default
0.0001
1
0.0003
0
0.0001
1
0.0003
0
0.0001
1
0.0003
0
0.0001
1
0.0003
0
1
60
-
Definite Time
1
4
Installation and Commissioning Manual
1MRS757488 H
Description
Amplitude
correction factor
for current
sensor, phase A
Phase correction
factor for current
sensor, phase A
Amplitude
correction factor
for current
sensor, phase B
Phase correction
factor for current
sensor, phase B
Amplitude
correction factor
for current
sensor, phase C
Phase correction
factor for current
sensor, phase C
Amplitude
correction factor
for current
sensor, residual
Phase correction
factor for current
sensor, residual
LEDs Reset
delay time
(incase no
external signal
received for
resetting). This is
applicable to OC
fault detection &
EF Protection
LEDs.
Self Reset
Method: Flashing
protection
indication LED is
reset
immediately
once the fault is
cleared.
Definite Time:
Flashing
protection
indication LED is
reset after the
definite time set
by LED reset
time delay.
Update interval
for metering
values
x500mSec
RIO600

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents